ABB i-bus
®
KNX
Commissioning
40 2CDC508171D0201 | SUG/U 1.1
No.
Function
Group object name
Data type
Flags
12
On/Off
Split unit
1 bit
DPT 1.001
C, W
Dependent on parameter
Always visible
This object switches the split unit on and off.
1 = split unit switches on
0 = split unit switches off
If a switching off delay is parametrized and activated, the split unit only switches off after the specified delay.
13
Status On/Off
Split unit
1 bit
DPT 1.001
C, R, T
Dependent on parameter
Enable group object "Status On/Off" 1-bit
This object indicates the status of the
On/Off
function.
1 = split unit is on
0 = split unit is off
If a switching off delay has been specified, the unit is not switched off until this has elapsed.
14
Deactivate On/Off delay
Split unit
1 bit
DPT 1.003
C, W
Dependent on parameter
Enable "On/Off delay" function
The
On/Off delay
function delays switching off the split unit (i.e. sending the infrared command) by the parametrized time.
Receipt of a telegram with the value 1 on the "Deactivate On/Off delay" object deactivates the switching off delay.
Telegram value
1 = Deactivates switching off delay
0 = Activates switching off delay
15
Forced operation
Function
1 bit
DPT 1.003
C, W
Dependent on parameter
Enable "Forced operation" function
Activating the
Forced operation
function (sending a telegram with the value 1 on the object) sets the split unit to its
parametrized state for forced operation.
When the
Forced operation
function is deactivated (telegram with the value 0 on the object), the lower-priority function
(Window contact) is evaluated, provided it is enabled.
If the
Window contact
function is not enabled or activated, the last non-priority command received via the KNX bus is
executed.
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......