ABB i-bus
®
KNX
Commissioning
44 2CDC508171D0201 | SUG/U 1.1
No.
Function
Group object name
Data type
Flags
28
Status Horizontal swing
Split unit
1 bit
DPT 1.003
C, R, T
Dependent on parameters
Enable "Swing" and
Enable group object "Status Swing" 1 bit
See Enable "Swing"
(horizontal and vertical), p. 24
This object indicates the status of horizontal swing.
1 = horizontal swing started
0 = horizontal swing stopped
29
Boost
Function
1 bit
DPT 1.001
C, W
Dependent on parameter
Enable "Boost" function
Receipt of a telegram with the value 1 on this object activates the
Boost
function. The split unit switches to the highest fan
speed and swing is activated.
After the parametrized duration the split unit returns to its original state.
30
Status Boost
Function
1 bit
DPT 1.001
C, R, T
Dependent on parameters
Enable "Boost" function and
Enable group object "Status Boost" 1 bit
This object indicates the status of the
Boost
function.
1 =
Boost
function is activated
0 =
Boost
function is deactivated
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......