ABB i-bus
®
KNX
Commissioning
SUG/U 1.1 | 2CDC508171D0201 21
Limit Setpoint temperature range
Options:
No
Yes
•
Yes:
Enables the 1-bit group object
Deactivate setpoint temperature limit.
Note
If you activate Setpoint temperature limit while the current setpoint temperature is outside the setpoint
temperature range, the setpoint temperature will be set to the upper or lower limit of the range.
Note
The setpoint temperature limit is activated after the download.
Note
However, activating the priority (Forced operation) takes the setpoint temperature limit into account.
Dependent parameters:
Max. heating setpoint temperature
Options:
16…23…32°C
Min. cooling setpoint temperature
Options:
16…18…32°C
This parameter sets limits for heating and cooling. If a temperature above the
Max. heating setpoint
temperature
or below the
Min. cooling setpoint temperature
is sent to the Split Unit Gateway, the
highest/lowest permissible value respectively is sent to the unit. Status values are updated accordingly.
Note
You need to check whether the split unit supports the required temperature range. You can read this
in the ETS app or refer to the manufacturer documentation for the split unit.
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......