ABB i-bus
®
KNX
Commissioning
38 2CDC508171D0201 | SUG/U 1.1
No.
Function
Group object name
Data type
Flags
4
Status Fan speed
Split unit
1 byte
DPT 5.001
C, R, T
Dependent on parameter
Enable group object "Status Fan speed" 1 byte
The fan speed status is always shown by the 1 byte object, even if Control fan speed with object parameter is set to
1 bit
up/down
on the
Split Unit settings
page.
The coding of the status object is dependent on the setting in the
Coding of 1 byte
parameter.
0%=Auto; 33%=Low, 66%=Medium, 100%=High
4
Status Fan speed
Split unit
1 byte
DPT 5.010
C, R, T
Dependent on parameter
Enable group object "Status Fan speed" 1 byte
The fan speed status is always shown by the 1 byte object, even if Control fan speed with object parameter is set to
1 bit
up/down
on the
Split Unit settings
page.
The coding of the status object is dependent on the setting in the
Coding of 1 byte
parameter.
0=Auto, 1=Low, 2=Med, 3=High
5
Fan up/down
Split unit
1 bit
DPT 1.007
C, W
Dependent on parameter
Control fan speed with object
When a telegram is received on this object, the fan speed reduces or increases by one speed.
Value 1: Increases fan speed
Value 0: Reduces fan speed
Available fan speeds are: Automatic, Low, Medium, High
If the fan reaches High, a further telegram with the value 1 has no effect.
If the fan is set to Automatic, a further telegram with the value 0 has no effect.
6
Operation mode
Split unit
1 byte
DPT 20.105
C, W
Dependent on parameter
Always visible
This object sets the operating mode for the split unit.
The operating modes set on receipt of a corresponding value are as follows:
0=Auto
1=Heating
3=Cooling
9=Ventilation
14=Drying
All other values are discarded.
Содержание i-bus KNX SUG/U 1.1
Страница 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...ABB i bus KNX Device technology 10 2CDC508171D0201 SUG U 1 1 2 3 Dimension drawing 2CDC072018F0016 ...
Страница 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Страница 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Страница 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Страница 55: ......