ABB i-bus
®
EIB / KNX
Device technology
2.2 ES/M
2.230.1
Electr. Switch Actuator
Module, 2-fold, 230 V
The 2-fold Electronic Switch Actuator Module is snapped into any module
slot of the Room Controller Basis Device. Using two semiconductor outputs,
it switches two resistive loads such as electrothermal valve drives for heating
control. The outputs are noise-free and wear-resistant. The nominal
switching voltage is 115 or 230 V.
Both the incoming supply and the internal voltage are supplied via the Room
Controller Basis Device. Contact is automatically established when the
modules are snapped in place.
2.2.1 Technical
data
Power supply / Incoming supply
– Internal supply
made available by the Room Controller Basis
Device, contact made via contact system on
base of module
– Incoming supply
90...264 V AC / DC, contact established via
contact surfaces at the front
Outputs
– 2 load circuits
Semiconductor outputs for resistive loads
Inrush current: max. 1 A
Continuous current: max. 700 mA
Connections
– Load circuits
2 x three-pole, plug-in screw terminals
– Wire ranges
0.2…2.5 mm
2
finely stranded
0.2…4.0 mm
2
single-core
Ambient temperature range
– Storage
-25 °C ... 55 °C
– Transport
-25 °C ... 70 °C
Design
– Type of installation
For snapping into the
Room Controller Basis Device
– Housing, colour
Plastic housing, anthracite, halogen-free
– Housing dimensions (WxHxD)
49 mm x 42 mm x 93 mm
– Weight
0.08 kg
CE norm
– in accordance with the EMC guideline and
the low voltage guideline
© 2004 ABB STOTZ-KONTAKT GmbH