ABB i-bus
®
EIB / KNX
Project design and programming
4.5.8.2
Detailed description of
the objects
Object: “Control value heating”: 1 byte (EIS6)
The heat output is specified via this object. The object value is sent e.g. by a
room thermostat.
Telegram value
“0”
No heat output
...
“255” Maximum heat output
Object: “Control value cooling”: 1 byte (EIS6)
The cooling capacity is specified via this object. The object value is sent e.g.
by a room thermostat.
Telegram value
“0”
No cooling capacity
...
“255” Maximum cooling capacity
Object: “Speed limitation”: 1 bit (EIS1)
The fan speed can be limited to a maximum value via this object. This
prevents the fan from exceeding a specific speed e.g. at night (noise
reduction).
Telegram value
“0”
Speed limitation not active
“1”
Speed limitation active
Object: “Forced operation”: 1 bit (EIS1)
A fan speed and valve position can be assigned to the fan coil controller via
this object and the controller is disabled. The fan speed and valve position
can be parameterised.
Telegram value
“0”
Forced operation not active
“1”
Forced operation active
Object: “Toggle heating/cooling”: 1 bit (EIS1)
This object is visible in the operating mode “2-pipe system, heating and
cooling” i.e. the fan coil unit only has one connection for supplying hot or
cold water. Via the object, the device receives information from the building
control system about whether hot or cold water is supplied. The object
“Control value heating” or “Control value cooling” is evaluated accordingly.
The object can be inverted.
Standard:
Telegram
value “0” Heat
“1”
Cool
Inverted:
Telegram
value “0” Cool
“1”
Heat
Objects: “Slave fan speed 2” to “ ... 5”: 1 bit (EIS1)
Via these objects, the master output controls further outputs which are used
for ventilation control. These outputs must be parameterised as slaves.
Telegram value
“0”
Fan speed switched off
“1”
Fan speed switched on
Object: “Slave valve”: 1 bit (EIS1)
This object is visible when using a 2-pipe system i.e. there is only one valve.
The object controls a further output which in turn controls the valve. The
output must be parameterised as a “Slave”. As soon as the fan is running at
speed 1 at least, the object value = “1”, otherwise it is “0”.
Telegram value
“0”
Valve closed
“1”
Valve
opened
© 2004 ABB STOTZ-KONTAKT GmbH
59