4.3.3 Parameter
window:
“Time”
The time functions such as the staircase lighting function, ON/OFF delay
and flashing can be set here. The parameter window is enabled under
“A: Function”.
Explanations about the time functions can be found in section 3.2.1. Please
note the function diagram in section 3.2.6.
Parameter: “Time function”
This parameter defines the type of the time function. It is possible to choose
between three types: “Staircase lighting”, “ON/OFF delay” and “Flashing”.
Selection: “Staircase lighting function”
The staircase lighting is switched on via an ON telegram. The staircase
lighting time is started when the function is activated. It is switched off when
the staircase lighting time elapses.
Parameter: “Duration of staircase lighting”
The operating time defines how long the staircase lighting is switched on
after an ON command.
Parameter: “Extending staircase lighting by multiple operation
(‘pumping up’)”
If a further ON telegram is received during the staircase lighting time, the
remaining staircase lighting time can be extended by a further period. The
maximum period can be set in this parameter.
In the setting “no”, the staircase lighting is reset on receipt of an ON
telegram (“retrigger function”).
Parameter: “Staircase lighting can be switched off”
It can be set here whether the staircase lighting is switched off prematurely
by an OFF telegram (“yes”) or whether the OFF telegram is ignored during
the staircase lighting time (“no”).
Note:
If the parameter value is “yes”, the staircase lighting can also be
switched off via the following other objects, if they lead to a
disconnection: “Logical connection”, “Preset”, “Lightscene”,
“Disable”, “Permanent ON”, “Forced operation”.
© 2004 ABB STOTZ-KONTAKT GmbH
28