ABB i-bus
®
EIB / KNX
Project design and programming
4.4.2 Parameter
window:
“Function”
Parameter: “Enable monitoring of the controller”
The cyclic monitoring of the room thermostat can be enabled here. The
failure of the thermostat can thus be detected. The output switches to fault
mode and moves to a defined position.
Parameter: “Enable function ‘forced operation’”
The forced operation of the output can be enabled here in order to move the
outputs to a specific position e.g. for inspection purposes.
Parameter: “Enable function ‘valve purge’”
The cyclic valve purge can be enabled here to prevent deposits from forming
in the valves.