Start-up 51
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
The table below gives the recommended drive parameter settings.
Output data
Modbus
register
Input data
Modbus
register
Control word
(4)00001
Status word
(4)00051
Speed reference
(4)00002
Speed actual value
(4)00052
Torque reference
(4)00003
Torque actual value
(4)00053
Constant speed
1)
(4)00004
(4)00005
Power
1)
(4)00054
(4)00055
Speed reference for
jogging function 1
1)
(4)00006
(4)00007
DC bus voltage
1)
(4)00056
(4)00057
1)
Example
Drive parameter
Setting for ACSM1
drives
Description
50.01 FBA ENABLE
Enable
Enables communication
between the drive and the
fieldbus adapter module.
50.02 COMM LOSS FUNC
Fault
2)
Enables fieldbus communication
fault monitoring.
50.03 COMM LOSS T OUT 3.0 s
2)
Defines the fieldbus
communication break
supervision time.
50.04 FBA REF1
MODESEL
Speed
Selects the fieldbus reference 1
scaling.
50.05 FBA REF2
MODESEL
Torque
Selects the fieldbus reference 2
scaling.
51.01 FBA TYPE
RS-485 COMM
1)
Displays the type of the fieldbus
adapter module.
51.02 FBA PAR2
(PROFILE)
1
(= ABB Enhanced)
Selects the ABB Drives -
Enhanced profile.
51.03 FBA PAR3
(STATION ID)
3
2)
Defines the address of the
device.
51.04 FBA PAR4
(BAUD RATE)
4
(= 115.2 kbit/s)
2)
Selects the baud rate of the link.
Note:
The baud rate of the
master has to be the same.
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...