Communication protocol 75
(4)20000…(4)29999
Drive Parameter Access (32-bit)
(not supported with ACS355)
Register Address = (4)20000 + 200 × Group +
2 × Index
Example for Drive Parameter 1.27:
(4)20000 + 200 × 1 + 2 × 27 = (4)20254
Note
: Addressing depends on the address
mode selected with parameter
12
in group A
(51/151, 54/154).
Register Address
1), 2)
Register Data (16-bit)
1)
6-digit register addressing ([4]00001) is used instead of 5-digit register
addressing ([4]0001) to describe register map. See section
Register
addressing
on page
70
for additional information.
2)
Register addresses of the 32-bit parameters cannot be accessed by
using 5-digit register numbers.