Start-up 37
08
OK messages
Read-only.
Shows the number of valid
messages which the drive has received.
0
0…65535
Number of valid messages
09
CRC errors
Read-only.
Shows the number of
messages with a cyclic redundancy check
(CRC) error which the drive has received.
If the number is high, check the CRC
calculation for possible errors.
Note:
High electromagnetic noise levels
may generate errors.
0
0…65535
Number of messages with a CRC error
10
UART errors
Read-only.
Shows the number of
messages which the drive has received
with other communication errors.
0
0…65535
Number of messages with other
communication errors
11
Word order
Selects in which order the 16-bit registers
of 32-bit parameters are transferred.
For each register (16-bit), the first byte
contains the high order byte and the last
byte contains the low order byte. The
covers holding register range of 1...65535.
1
= HILO
0
= LOHI
The first register contains the low order
word and the second register contains the
high order word.
1
= HILO
The first register contains the high order
word and the second register contains the
low order word.
12
Address mode
Defines the mapping between parameters
and holding registers in the 0...65535
Modbus register range.
0 =
Mode 0
No.
Name/Value
Description
Default
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...