Start-up 53
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal)
→
READY TO SWITCH ON.
•
Enter 47Fh (1151 decimal)
→
OPERATING (Speed mode)
or
C7Fh (3199 decimal)
→
OPERATING (Torque mode).
34.05 EXT2 CTRL MODE1
Torque
Selects torque control as the
control mode 1 for external
control location 2.
1) Read-only or automatically detected/set
2) Example
Drive parameter
Setting for ACSM1
drives
Description