Start-up 47
5102 FB PAR 2
(PROFILE)
1
(= ABB
Enhanced)
Selects the ABB Drives -
Enhanced profile.
5103 FB PAR 3
(STATION ID)
3
2)
Defines the address of the device.
5104 FB PAR 4
(BAUD RATE)
4
(= 115.2 kbit/s)
2)
Selects the baud rate of the link.
Note:
The baud rate of the master
has to be the same.
5105 FB PAR 5
(PARITY)
0
(= 8 None 1)
2)
Defines the use of parity and stop
bit(s) and the data length.
Note:
The parity setting of the
master has to be the same.
5106 FB PAR 6
(MODBUS TIMEOUT)
10
2)
Sets the communication timeout
as 1 second.
5107 FB PAR 7
(TIMEOUT MODE)
2
(=Ctrl write)
2)
The timeout feature monitors the
updating of the Control word and
Reference 1.
3018 COMM FAULT FUNC
1
= FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT TIME
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
5401 FBA DATA IN 1
106
2)
Power
5402 FBA DATA IN 2
107
2)
DC bus voltage
5501 FBA DATA OUT 1
1202
2)
Constant speed 1
5502 FBA DATA OUT 2
1203
2)
Constant speed 2
5127 FBA PAR REFRESH
1
= REFRESH
Validates the FSCA-01
configuration parameter settings.
9904 MOTOR CTRL
MODE
2
= VECTOR:
TORQ
Selects the vector control mode as
the motor control mode.
1001 EXT1 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1002 EXT2 COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
Drive parameter
Setting for
ACS355 drives
Description
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...