Diagnostics 85
Internal error code registers
A Modbus query can fail in many ways in the drive. The Modbus
standard does not specify detailed error descriptions. In addition to
the standard error codes, the FSCA-01 module provides an
internal error register area for more detailed diagnostics.
The internal error register area is used if Modbus error code 0x04
occurs. The registers contain information about the last query. You
can figure out the reason of the failure by reading the registers.
The internal error register is cleared when a query has finished
successfully.
NETWORK
Off
No communication
Flashing green
Communication activity on the interface
Orange
Configuration error
Flashing green,
alternating with
flashing orange
Parity error
Flashing orange
Data lines DATA_B and DATA_A are
connected crosswise. Swap the data
lines at connector X1 or at the master
station.
Address
Registers (16-bit word)
(4)00090
Reset internal error registers (0 = Do nothing, 1 = Reset)
(4)00091
Function code of the failed query
(4)00092
Internal error code; see the error number.
(4)00093
Failed register
Name
Color
Function/state
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...