34 Start-up
Drive configuration
The following information applies to all drive types compatible with
the adapter module, unless otherwise stated.
Modbus/RTU connection configuration
After the adapter module has been mechanically and electrically
installed according to the instructions in chapters
Mechanical
installation
and
Electrical installation
, you must prepare the drive
for communication with the module.
The detailed procedure of activating the module for Modbus/RTU
communication with the drive depends on the drive type. Normally,
you must adjust a parameter to activate the communication. See
the drive-specific start-up procedures starting on page
45
.
Once communication between the drive and the adapter module
has been established, several configuration parameters are copied
to the drive. These parameters are shown in the tables below and
must be checked first and adjusted where necessary.
Note that not all drives display descriptive names for the
configuration parameters. To help you identify the parameters in
different drives, the names displayed by each drive are given in
grey boxes in the tables.
Note:
The new settings take effect only when the adapter module
is powered up the next time or when the fieldbus adapter refresh
parameter is activated.
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...