Start-up 39
13...
23
Reserved
These parameters are not used by the
adapter module.
N/A
24
Protocol check
Read only.
Shows whether the parameters
of the selected communication protocol
have been loaded to the module.
- If the value of this parameter corresponds
to the setting of par.
25
Protocol
, it means
that the parameters have been loaded.
- If the value of this parameter differs from
the setting of par.
25
, load the parameters
by setting par.
27
FBA par refresh
to
1
=
Refresh / Configure.
1
0…5
Communication protocol check
25
Protocol
Selects the communication protocol for the
network connection.
1
= Modbus
0
No protocol selected
1
= Modbus
Modbus/RTU protocol selected
2
= N2
N/A
3
= FLN
N/A
4
= BACnet
N/A
5
= DCP
N/A
26
Protocol sw ver
Read only.
Shows the software version of
the communication protocol currently
selected.
N/A
Version of the communication protocol
27
FBA par refresh
Validates any changed adapter module
configuration parameter settings. After
refreshing, the value reverts automatically
to
0
= Done.
Note:
This parameter cannot be changed
while the drive is running.
0
= Done
0
= Done
Refreshing done
1
= Refresh /
Configure
Refreshing
No.
Name/Value
Description
Default
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...