54 Start-up
Starting up ACS880 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter
50.01 FBA A enable
to Enable.
3. With parameter
50.02 FBA A comm loss func
, select how the
drive reacts to a fieldbus communication break.
Note that this function monitors both communication between
the fieldbus master and the adapter module and
communication between the adapter module and the drive.
4. With parameter
50.03 FBA A comm loss t out
, define the
time between communication break detection and the selected
action.
5. Select application-specific values for parameters
50.04
…
50.11
. Examples of appropriate values are shown in
the tables below.
6. Set the FSCA-01 configuration parameters in group
51
.
•
Select the communication protocol with parameter
51.25
and profile with parameter
51.02
.
•
Configure the network settings with parameters
51.03
…
51.05
.
•
With parameters
51.06
and
51.07
, select how the adapter
module detects fieldbus communication breaks.
7. Define the process data transferred to and from the drive in
FSCA-01 configuration parameter groups
52
and
53
.
Note 1:
The adapter module assigns the Control word, Status
word, references 1…2 and actual values 1…2 automatically to
Modbus registers. Process data groups are not available in the
ABB Drives - Classic communication profile.
Содержание FSCA-01
Страница 1: ... OPTION FOR ABB DRIVES CONVERTERS AND INVERTERS FSCA 01 RS 485 adapter module User s manual ...
Страница 4: ......
Страница 8: ...8 Table of contents ...
Страница 18: ...18 About the manual ...
Страница 24: ...24 Overview of the RS 485 network and the FSCA 01 module ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 68: ...68 Communication profiles ...
Страница 82: ...82 Communication protocol ...