Electromagnetic Flowmeter
COPA-XE / MAG-XE
9.2.3
Electrical Connection Area
!
Note:
When installing the signal/excitation cable at the
flowmeter primary a water trap should be provided
(Fig. 32).
9.2.4
Installations for Protection Class IP 68
The max. submergence depth for flowmeter priamries designed
for Protetion Class IP 68 is 5 m. A hose enclosed connector is
used in place of the standard PG connector. The signal/
excitation cable must be enclosed in the 1/2” hose from the
connection box to above the maximum submergence level
(Fig. 33). Above this level the cable is installed using the cable
connector included with the shipment in a water tight manner.
The hose is then attached to the hose connector using the
threaded clamp ring. Finally the connection box should be
carefully secured.
Supply Power{
In-/Outputs
SE-Terminal
Ground
Signal/Excitation Cable
Fig. 31
Converter, Field Mount Housing
View into Connection Box
Water Trap
Fig. 32
Cable Installation with a Water Trap
Max.
Subm
ergence Dept
h
5
m
Water Tight Cable Connector
Signal/Excitation Cable
Install the hose above the submergence
level and seal the signal/excitation cable
using the cable connector.
Fig. 33
Installation IP 68 (Hose Connector)