![ABB AX400 Series Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/abb/ax400-series/ax400-series_user-manual_3535680063.webp)
61
SPECIFICATION…
Relay Outputs – On/Off
Number of relays
Three, supplied as standard
Five, when ordered with option card
Set point adjustment
Fully configurable as normal or failsafe high/low or
diagnostic alert
Hysteresis of reading
Programmable 0 to 5% in 0.1% increments
Delay
Programmable 0 to 60s in 1s intervals
Relay contacts
Single-pole changeover
Rating 5A, 115/230V AC, 5A DC
Insulation
2kV RMS contacts to earth/ground
Access to Functions
Direct keypad access
Measurement, maintenance, configuration, diagnostics or
service functions
Performed without external equipment or internal jumpers
Power supply
Voltage requirements
85 to 265V AC 50/60 Hz
24V AC or 12 to 30V DC (optional)
Power consumption
<10VA
Insulation
Mains to earth (line to ground) 2kV RMS
Safety
General safety
EN61010-1
Overvoltage Class II on inputs and outputs
Pollution category 2
Cable Entry Types
Standard
5 or 7* x M20 cable glands
N. American
7 x knockouts suitable for 1/2 in. Hubble gland
Hazardous area approvals
CENELEC ATEX IIG EEx n IIC T4 Pending
FM non-incendive Class I Div. 2 Groups A to D Pending
CSA non-incendive Class I Div. 2 Groups A to D
Pending
Mechanical Data
Panel-mount versions
IP66/NEMA4X
Dimensions 192mm high x 230mm wide x 94mm deep
(7.56 in. high x 9.06 in. wide x 3.7 in. deep)
Weight 1kg (2.2 lb)
Panel-mount versions
IP66/NEMA4X (front only)
Dimensions 96mm x 96mm x 162mm deep
(3.78 in. x 3.78 in. x 6.38 in. deep)
Weight 0.6kg (13.2 lb)
Languages
Languages configurable
English
French
German
Italian
Spanish
SS/AX4PH Issue 1