90 Maintenance
1. Disconnect the drive from the AC power line and DC/DC converter from the energy
storage and obey the instructions in section
on page
See
Disconnecting the DC/DC converter with DC switch/disconnector (F286)
2. Open the cubicle door.
3. Undo the screws of the shroud in the upper part of the cubicle. Remove the shroud.
4. Unplug the terminal block [X50] on top of the module.
5. Disconnect the two DC busbars on top of the module. Be careful not to drop the
screws inside the module! Make note of the order and position of the screws and
washers.
6. Remove the cover on the fiber optic connectors in front of the module. Unplug the fiber
optic cables [X52, X53]. Move the disconnected wiring aside.
7. C121, marine construction: If a marine support plate is installed in front of the
converter and filter modules, undo the screws that fasten the marine support to the
modules (a). Loosen the screws that fasten the support to the corner posts (do not
remove the screws) (b). Remove the support.
Note:
Reinstall the converter and filter module screws (b) before removing the
modules from the cubicle.
8. Remove the two screws that fasten the bottom of the module to the base of the
cabinet.
9. Install the module pull-put ramp: lift the module pull-out ramp against the cabinet base
so that the hooks of the base go into the ramp’s holes.
10. Remove the two fastening screws that fasten the top of the module to the cabinet
frame.
11. Pull the module carefully out of the cabinet along the ramp. While pulling on the
handle, keep a constant pressure with one foot on the base of the module to prevent
the module from falling on its back.
Lift the module by the upper part only
using the lifting holes at the top!
Mind your fingers! Keep fingers
away from the edges of the
front flange of the module!
Support the top and bottom
of the module while
replacing!
Содержание ACS880-1607
Страница 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Страница 4: ......
Страница 12: ...12 Introduction to the manual ...
Страница 34: ...34 Mechanical installation ...
Страница 40: ...40 Guidelines for planning electrical installation ...
Страница 52: ...52 Electrical installation ...
Страница 68: ...68 Start up ...
Страница 80: ...80 Maintenance 7 3 4 5 6 ...
Страница 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Страница 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Страница 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Страница 93: ...Maintenance 93 9 8 8 10 11 ...
Страница 96: ...96 Maintenance 4 8 6 7 5 3 ...
Страница 97: ...Maintenance 97 9 ...
Страница 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Страница 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Страница 120: ...120 Dimensions Location and size of input terminals Frame 1 R8i bottom cable entry Frame 1 R8i top cable entry ...
Страница 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...