36 Guidelines for planning electrical installation
Selecting the energy storage
WARNING!
ABB is not responsible for the customer ‘s energy storage selection or
protection of the energy storage.
The customer must equip the DC/DC converter with a suitable energy storage system:
•
Dimension the energy storage so that it withstands the required current cycles and the
stored energy is sufficient. Take the depth of discharge into account in energy storage
lifetime calculations.
•
The energy storage must withstand the current ripple of the converter. See
page
•
The output voltage (energy storage voltage) is not allowed to exceed the DC/DC
converter DC bus voltage. Add sufficient voltage margin in the design to prevent this in
case of voltage dips or grid faults.
•
The recommended energy storage operating voltage is:
U
storage
= 150 V … 80% of
U
DC
•
The DC voltage values of the drives are:
•
with diode supply units (ACS880-307 +A003, ACS880-307 +A018):
•
with IGBT supply units (ACS880-207) typically
•
with regenerative rectifier units (ACS880-907):
•
where
•
We recommend to measure the energy storage voltage. If you use a super capacitor
as the energy storage, voltage measurement is obligatory. If the converter is equipped
with the BAMU voltage/current measurement unit (G442), the converter
measures its output voltage (and thus also the ES voltage) automatically. You do not
need any additional measurement for the converter. If there is no BAMU, you must
arrange the voltage measurement separately, and send the measured value to the
converter control program, eg, via a fieldbus communication (if in use), or by some
other means. For more information, see section
Energy storage voltage measurement
and estimation
and parameter description in
ACS880 DC/DC converter control
program firmware manual
(3AXD50000024671 [English]).
•
The energy storage must have a disconnecting device and contactor. See
Disconnection of energy storage at the storage end
and
U
DC
= 1.35 ×
U
AC
U
DC
= 1.41 ×
U
AC
(can be changed with supply unit parameter group 123 DC
volt ref)
U
DC
= 1.35 ×
U
AC
U
DC
=
Drive DC voltage (in the DC bus)
U
AC
=
Drive input voltage (AC)
Содержание ACS880-1607
Страница 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Страница 4: ......
Страница 12: ...12 Introduction to the manual ...
Страница 34: ...34 Mechanical installation ...
Страница 40: ...40 Guidelines for planning electrical installation ...
Страница 52: ...52 Electrical installation ...
Страница 68: ...68 Start up ...
Страница 80: ...80 Maintenance 7 3 4 5 6 ...
Страница 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Страница 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Страница 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Страница 93: ...Maintenance 93 9 8 8 10 11 ...
Страница 96: ...96 Maintenance 4 8 6 7 5 3 ...
Страница 97: ...Maintenance 97 9 ...
Страница 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Страница 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Страница 120: ...120 Dimensions Location and size of input terminals Frame 1 R8i bottom cable entry Frame 1 R8i top cable entry ...
Страница 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...