112 Practical examples
32.38 P/Q UNSYM ENA
60%
Control program IWXR7300 (or newer) parameters:
40.01 RT ENABLE
ON
40.02 NAMU BOARD ENABLE
ON
40.04 PHASE MEAS ENA
ON
40.05 UAC CTRL SEL
RMS VOLTAGE
40.09 RT U/Un MOD STOP
9.99999%
40.10 RT U/Un LEVEL1
90%
40.11 RT U/Un LEVEL2
0%
40.12 RT U/Un LEVEL3
70%
40.13 RT U/Un DELTA t1
3000 ms
40.14 RT U/Un DELTA t2
600 ms
40.15 RT U/Un DELTA t3
20000 ms
40.20 TRP VOLT PEAK
130%
40.21 TRP VOLT LEV
120%
40.22 TRP VOLT TIME
20 ms
40.23 TRP VOLT SEL
RMS VOLTAGE
41.01 GRID SUPPORT MODE
OFF
41.02 GS HIGHEST U ENA
ON
41.03 GS U/Un LEVEL 1
100%
41.04 GS U/Un LEVEL 2
50%
41.05 GS U/Un LEVEL 3
25%
41.06 GS U/Un LEVEL 4
15%
41.07 GS IQREF LEVEL 1
0%
41.08 GS IQREF LEVEL 2
100%
41.09 GS IQREF LEVEL 3
100%
41.10 GS IQREF LEVEL 4
100%