System description 27
Overview of converter interfaces
The WTC controls the converter using its main control word. For more information, refer to
section
ABB Drives communication profile
on page
.
The start-up procedure of the converter is recommended to be proceeded with the
DriveWindow PC tool. For information on using the DriveWindow, see
DriveWindow 2
user’s manual
[3BFE64560981 (English)].
With optional Ethernet adapter module (NETA), the user can remotely
•
monitor the converter
•
read and adjust converter parameter values
•
read status information and actual values from the converter
•
set up and monitor (numerically or graphically) the data logger and save its
content to a file
•
read and clear the contents of the fault log and save it to a file
•
control the converter (not recommended remotely)
•
give control commands (Start, Stop, Run enable, etc.) to the converter
•
feed a generator speed or torque reference to the converter
•
reset converter faults.
For more information, see
NETA-01 Ethernet adapter module user’s manual
[3AFE64605062 (English)].