82 Practical examples
Note:
Some generator manufacturers give equivalent circuit data for delta connection. In
that case the given reactance values must be divided by three.
Transformation ratio between the
stator and the rotor. Defined when
rotor shaft is mechanically locked
and nominal stator voltage is fed to
the stator windings.
99.15 MOTOR OPEN CKT V
Note:
Rotor open-circuit voltage.
Long time rotor current limitation
99.16 MOTOR NOM IM
Note:
I
M
is not needed in the slip ring generator model.
I
M
is used for
defining the maximum allowed long time rotor current limit.
Stator resistance (
R
s
)
99.21 Rs
Stator leakage reactance
99.22 X1S
Rotor leakage reactance
99.23 X2S
Mutual reactance
99.24 XM
Note:
See the equation on page
Rotor resistance (
R
r
)
99.25
Rr
Note:
R
r
must be referred to the stator frame. See the equation on
page
.
Generator data