48 Start-up with low voltage stator
Test active crowbar functioning with manual trigger:
Select parameter 06.11 CB BRIDGE VOLTAGE and 06.12 CB IGBT
VOLTAGE signals to be monitored with DriveWindow datalogger 2.
Use the following DriveWindow settings:
• Interval = 2
• Trigg Conditions = Level, Falling edge
• Trig Variable = 06.11 CB BRIDGE VOLTAGE
• Trigg Level = 700
Start the rotor-side converter in local mode with the DriveWindow
START button. (Rotor does not need to rotate.)
Start the DriveWindow datalogger after the DC link has been charged.
Set parameter 21.08 MANUAL TRIGGER first to OFF and then to
ON.
Note:
16.01 PARAM LOCK must be set OFF in order to accept
command.
Upload datalogger.
If the measured diode bridge voltage (06.11 CB BRIDGE VOLTAGE)
drops for a short time when triggered, the active crowbar functions.
06.11 CB BRIDGE
VOLTAGE
06.12 CB IGBT VOLTAGE
21.08 MANUAL TRIGGER
The following figure shows the active crowbar voltages when manual triggering is used.
Stop the converter with the DriveWindow STOP button.
Set the Low Voltage Ride Through function and Grid Support function
parameters. Values must be set according to the selected grid code.
See
ACS800-67(LC) doubly-fed induction generator control program
firmware manual
[3AUA0000071689 (English)].
Grid support function can
be tuned by parameters in
group 32 LV RIDE-
THROUGH.
Grid-side converter and DC chopper test
If the converter is NOT equipped with a DC chopper, continue to the next section.
NUIM board in use (grid-side converter control program
IXXR72xx):
• Set parameter 58.01 ADAPT PROG CMD to STOP. (grid-side
converter par.)
58.01 ADAPT PROG CMD
NAMU / BAMU board in use (grid-side converter control program
IWXR74xx):
• Set parameter 58.01 ADAPT PROG CMD to STOP. (grid-side
converter par.)
58.01 ADAPT PROG CMD
Содержание ACS800-67
Страница 1: ...ABB wind turbine converters System description and start up guide ACS800 67 wind turbine converters ...
Страница 4: ......
Страница 76: ...76 Start up with medium voltage stator ...
Страница 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Страница 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Страница 118: ...118 Tracing the source of warnings limits and faults ...
Страница 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...