44 Start-up with low voltage stator
Enter the number of encoder pulses.
50.04 PULSE NR
Select the communication profile used by the converter. For more
information see section
ABB Drives communication profile
on page
.
16.11 COMM PROFILE
Set parameter limits in group 20 LIMITS according to the process
requirements.
20.05 USER POS TORQ LIM defines the motoring torque limit
20.06 USER NEG TORQ LIM defines the generating torque limit.
20.05
USER POS TORQ
LIM
20.06 USER NEG TORQ
LIM
20.21 SWITCH ON
SPEED
20.22 SWITCH OFF
SPEED
Select the reactive power reference type
(PERCENT/KVAR/PHII/COSPHII).
23.04 REACT POW REF
SEL
Set the stator overcurrent trip limit.
During commissioning when the converter runs in local control mode
without torque references, set parameter value to approximately
500 A. After commissioning set parameter value to 0 A.
30.04 STATOR CURR
TRIP
Set the over/underspeed limits.
30.09 OVERSPEED LIMIT
30.10 UNDERSPEED
LIMIT
Activate the external communication by setting parameter 98.02
COMM MODULE to FBA DSET 10.
98.02 COMM MODULE
Set the fieldbus adapter data according to the used external control
system.
Note:
The configuration parameters are not visible if the module is
not connected or activated in the control program. See appropriate
adapter hardware manual.
51 MASTER ADAPTER
Activate the fieldbus adapter supervision toggle bit (if needed).
70.25 TOGGLE BIT SEL
70.26 TOGGLE
ADDRESS SEL
Define the current limit and breaking device type for the grid
connection between stator and grid.
0 A = air circuit breaker used for disconnecting stator from grid.
> 0 A = contactor is used for disconnecting stator from grid.
If stator current exceeds given value at the time disconnection is
requested, then the wind turbine converter first opens the breaker in
front of the contactor, then the contactor shortly later.
20.27 CONT OPEN CUR
Check that the breaker/contactor configuration of the converter is set
correctly according to the delivery. For configurations available and
corresponding parameter settings, see section
16.20 GRID CONNECT
MODE
If the parameter 16.20 GRID CONNECT MODE selection is
MCB1+MCB3/C:
To set certain breaker related fault logger texts
correctly, set parameter 99.01 LANGUAGE to DEUTSCH.
99.01 LANGUAGE
Содержание ACS800-67
Страница 1: ...ABB wind turbine converters System description and start up guide ACS800 67 wind turbine converters ...
Страница 4: ......
Страница 76: ...76 Start up with medium voltage stator ...
Страница 99: ...Practical examples 99 1 4 4 3 2 5 6 7 ...
Страница 106: ...106 Practical examples Counterclockwise rotation at drive end D end Power cabinet Encoder ...
Страница 118: ...118 Tracing the source of warnings limits and faults ...
Страница 120: ...Contact us www abb com windconverters 3AUA0000095094 Rev B EN 2017 12 31 ...