43
Startup technician must check for proper
motor rotation for compressors, condenser
fan motors, and pumps and check fan motor
amperage listed on the motor nameplate is
not exceeded. Motor overload protection may
be a function of the variable frequency drive
and must not be bypassed. Variable
frequency drives are programmed to
automatically rotate the fan in the correct
rotation. Do not rely on fan with variable
frequency drives for compressor rotation.
Note:
All units are factory wired for
208/230V, 460V, or 575V. If unit is to be
connected to a 208V supply, the transformer
must be rewired to 208V service.
Wire control signals to the unit’s low voltage
terminal block located in the controls
compartment.
If any factory installed wiring must be
replaced, use a minimum 221°F (105°C) type
AWM insulated conductors.
Supply voltage must be within the min/max
range shown on the unit nameplate. Available
short circuit current should not exceed the
short circuit current rating (SCCR) shown on
the unit nameplate.
CONVENIENCE OUTLETS AND
SERVICE LIGHTS
Convenience outlet and service light
circuits are wired to the incoming
power side of the disconnect. These
circuits will remain powered even
when unit disconnect is off.
WARNING
Installing Contractor is responsible for
proper sealing of the electrical and
gas entries into the unit. Failure to seal
the entries may result in damage to
the unit and property.
CAUTION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. High pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit power
connection.
CAUTION
BURNING FOAM INSULATION IS
TOXIC! Do not cut holes into any
foam insulated panels with any flame
producing cutter such as a plasma
cutter or cutting torch.
WARNING
Three phase voltage imbalance will
cause
motor
overheating
and
premature failure.
CAUTION
Содержание LZ Series
Страница 2: ......
Страница 27: ...27 Figure 6 Concrete Pad Mounting with Dimensions Figure 7 LZ Base ...
Страница 36: ...36 Figure 17 Typical Flue Vent Piping ...
Страница 40: ...40 Figure 24 Typical Vertical Vent Piping Figure 25 Vertical Termination of Air Intake and Vent Piping ...
Страница 83: ...83 ...
Страница 84: ...84 ...
Страница 95: ...95 Flo Trex Cross Section ...