Instruction manual BFM
31
is
A.O. Smith prescribes the use of a concentric roof or wall flue terminal,
exclusively of a type approved for the appliance. Use of an incorrect roof or wall
flue terminal can cause the installation to malfunction.
You must also fulfil the following requirements:
•
The maximum permissible length of chimney pipe (A+B+C) is 7 metres.
•
The maximum permissible number of 45° or 90° bends is 2.
•
If you are using a horizontal pipe, you must mount it with a minimum run-off
of 5 mm per running metre of pipe towards the appliance!
•
The transition piece to convert the air supply and chimney flue from parallel
to concentric must be installed immediately before the wall or roof flue
terminal.
•
The intake duct of the air supply must be approximately the same as the
chimney flue.
•
Make sure that the chimney flue discharges into an area approved for this
type of appliance.
See the figures. Wall flue terminal
(3.9.8 "Concentric wall flue terminal BFM100,
120")
and Roof flue terminal
(3.9.10 "Concentric roof flue terminal BFM 100,
120")
for examples of installation.
3.9.8
Concentric wall flue terminal BFM100, 120
Wall flue terminal
.
B
A
IMD-0226 R1
Содержание BFM - 100
Страница 1: ......
Страница 2: ......
Страница 4: ...4 Instruction manual BFM gis ...
Страница 10: ...Introduction 10 Instruction manual BFM 1 gis ...
Страница 16: ...Working principle of the appliance 16 Instruction manual BFM 2 gis ...
Страница 42: ...Conversion to a different gas category 42 Instruction manual BFM 4 is ...
Страница 48: ...Draining 48 Instruction manual BFM 6 gis ...
Страница 52: ...Status of the appliance 52 Instruction manual BFM 8 gis ...
Страница 54: ...Starting and running 54 Instruction manual BFM 9 gis ...
Страница 56: ...Shutting down 56 Instruction manual BFM 10 gis ...
Страница 62: ...is Instruction manual BFM 62 ...
Страница 72: ...Electrical diagram 72 Instruction manual BFM 14 is ...
Страница 74: ...0306 723 4 0 UK Index Instruction manual BFM ...