5

INSTALLATION

to negative battery terminal.  Upon proper connection, test alarm will 

sound.  Press alarm reset to silence.  This indicates proper charger to 

battery connection.  

CAUTION

 Correct battery hook up is essential 

for operation of the system.  Use nuts supplied with battery and eyelet 

connectors on battery wire leads.  The positive terminal is the larger 

stud, 3/8" (10 mm) diameter.  The smaller stud, 5/16" (8 mm) diameter 

is the negative terminal.  Apply grease to the terminals to help prevent 

corrosion.

  7.  Connect the black lead from the pump to the negative (-) battery terminal.   

Connect the white lead from the switch to the positive (+) battery terminal.

  8.  Close battery box and secure cover.  
  9.  Plug the control power cord into the 115 V wall outlet.  The primary sump 

pump and the control charger should be on separate circuits.

 10.  Reconnect power to primary sump pump.
 11.  Optional: A dongle may be used to input a name and number into the 

charger for service information to the end user. Contact Customer 

Support for more information.

 12.  Optional: On the bottom of the charger there is a pair of dry contacts to 

signal an auxiliary device of a low battery, high water and reverse polarity 

alarm condition. This simple 2-wire connection is rated at a maximum of 

24V AC/DC and 0.5 amps.  It can be used with an auto-dialer (such as 

the Zoeller 10-2616), alarm or home security system.  Read the auxiliary 

equipment's documents for further instructions.

  1.  The preferred method of installation for backup pumps is shown in figure 1.  

The installation kit includes one check valve for installing with the backup 

pump discharging into the primary pump outlet pipe.  An additional check 

valve is incorporated in the discharge of the backup pump.

  2.  Select location for battery and control charger.  Control charger must be 

within 6' (1.8 m) of a 115 V wall outlet and within 6' (1.8 m) of pump and 

basin.  Connect to a separate circuit, different than the primary pump.

  3.  Make certain the float switch clamp is tight on the pipe to avoid slippage.    

Ensure that the “off” level of the float is 1" (25 mm) min. above the discharge 

tee of the DC backup pump (see figure 1).  Position pumps in the sump and 

move float up and down, making sure of free movement without interference 

from any obstructions inside the sump or lid.  Very shallow sumps may 

require some adjustment to avoid overfilling or backing up of water into the 

sump inlet.  The float switch can be moved on the discharge pipe or the 

rubber stops can be adjusted as necessary.  Cut extra float rod length below 

lower float stop to prevent debris from interfering with float operation (see 

figure 2).

  4.  Mount DC control charger to the wall.  If more convenient, the control 

charger may be set on a nearby shelf or ledge.  The control charger should 

be located 3' (0.9 m) or 4' (1.2 m) above the sump.  

  5.  Connect the green sensor wire to the sensor connector (figure 3).   
  6.  Connect the leads from the control charger to the battery terminals.  

White  positive (+) lead to positive terminal and black negative (-) lead 

INITIAL START-UP AND OPERATION

  1.  Test the installation for leaks by running water into the sump allowing for 

normal operation of the primary pump.

  2.  Check the control charger.  The red power on light will be lit when the unit 

is plugged into the 115 V wall outlet. The yellow/green light will indicate 

the condition of the battery.

  3.  Disconnect primary pump before touching any component in the sump pit.
  4.  Lift float switch.  The DC backup pump will run and the alarm will sound.  

Lower float switch immediately after pump has started running.  Pump is 

running dry during initial check out for several seconds. 

  

CAUTION

 Continuous dry running may cause overheating and damage 

the pump seals.  Upon release of the float switch, the pump will shut off. 

Press the reset button to turn the alarm off.

  5.  Complete the final testing of your installation by disconnecting the power to 

the primary pump and the control charger by removing the plugs from the 

115 V wall outlets.  Run water into the sump until the DC backup pump is 

activated by the float switch.  Check all connections for leaks.

  6.  Push alarm reset switch when pump is running.  This will silence the alarm.  

The pump will continue to run.

  7.  Reconnect the control charger and your primary pump to the AC wall outlets.  

The primary pump should come on and lower the water level in the sump 

back to the normal operating level and shut off.  Both primary and backup 

systems are now ready for use.

  8.  The battery charged and charging LED’s will alternate during normal 

charging operation.

MAINTENANCE

1.  Inspect and test the system for proper operations at least every 3 months.

 

(a) Red power on indicator light should be “on” indicating AC 

power is on.

 

(b)  Unplug primary pump and the control charger from power supply.

 

(c)  Fill sump with water to the “on” level for the DC pump. Allow 

pump to run a few minutes.

 

(d)  The alarm will sound approximately 5 seconds after the pump 

starts to run.

 

(e)  Push alarm reset switch.  The alarm will go “off”.

 

(f)  Pump will shut off after water level is lowered and the float drops 

to the off position.

2.  Plug the control charger and the primary pump into the wall outlet.

 

(a)   The primary pump will come on and lower the water to the

 

   normal operating level and shut off.

 

(b)   The “yellow” charging light should be on.  The charger is replacing 

the energy consumed during the test.  The “green” light will come 

on after the charger has replaced the energy consumed during 

the test.

3.  Add distilled water to battery when necessary per battery manufacturer's 

instructions. 

 

CAUTION

 Battery acid is dangerous.  Take proper safety 

precautions.  Do not splash the acid.  

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

Summary of Contents for ProPak 507

Page 1: ...dinances 6 FOR YOUR PROTECTION ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING Single phase pumps are supplied with a 3 prong grounded plug to help protect you against the possibility of electrical shock DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE GROUND PIN The 3 prong plug must be inserted into a mating 3 prong grounded receptacle If the installation does not have such a receptacle it...

Page 2: ...batteries We offer both a Water Acid Deep Cycle Battery and maintenance free AGM battery which can run the pump continuously for over 7 hours These times are based on continuous pumping at 8 2 4 mm of static head Actual times will vary depending on static head volume of water entering the pit and the condition of the battery Follow these recommendations Use a B C I size 27 deep cycle battery 175 m...

Page 3: ...TALLATION FOR ALL APPLICATIONS EASY DO S DON TS FOR INSTALLING A SUMP PUMP 1 DO read thoroughly all installation material provided with the system 2 DO inspect system for any visible damage caused by shipping Contact dealer if system appears to be damaged 3 DO clean all debris from the sump Be sure that the pump will have a hard flat surface beneath it DO NOT install on sand gravel or dirt 4 DO be...

Page 4: ...HTEN ONLY WEEP HOLE MUST BE VISIBLE FLOAT SWITCH DC PUMP M73 PRIMARY PUMP CLAMP TYPICAL INSTALLATION EXPLODED VIEW OF PUMP SYSTEM FIGURE 1 R R DC PUMP PLUMBED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE 1 25 MM MIN ABOVE CENTER OF TEE SEE INSTALLATION NOTE 3 VERIFY WEEP HOLE IS VISIBLE SEE PUMP INSTALLATION INSTRUCTIONS CHECK VALVE WEEP HOLE PROVIDED PUM...

Page 5: ...may be set on a nearby shelf or ledge The control charger should be located 3 0 9 m or 4 1 2 m above the sump 5 Connect the green sensor wire to the sensor connector figure 3 6 Connect the leads from the control charger to the battery terminals White positive lead to positive terminal and black negative lead INITIAL START UP AND OPERATION 1 Test the installation for leaks by running water into the...

Page 6: ...ECKLIST EXPLODED VIEW DC PUMP All installations must comply with all applicable electrical and plumbing codes including but not limited to National Electrical Code local regional and or state plumbing codes etc Not intended for use in hazardous locations SK2501 BATTERY BOX 12 VOLT MARINE BATTERY SUPPLIED BY USER FIG 5 DC BACK UP PUMP CLAMP FLOAT SWITCH WHITE LEAD TO POSITIVE BLACK LEAD TO DC PUMP ...

Page 7: ...condition a mixture of air and water may cause a complete or partial air lock and reduce or stop the flow of water in the discharge pipe b Baffle the incoming stream of water to reduce turbulence Diverting water stream against wall of basin usually corrects an air lock problem 7 Water level stays high DC Pump continues to run a Battery is low b If power has been restored and water in sump remains ...

Page 8: ...CYCLED CHARGING ALARM RESET LOW BATTERY ALARM OFF ALARM CONTACTS GREEN LEAD TO FLOAT SWITCH BLACK LEAD WHITE LEAD FIGURE 4 SK2503 FIGURE 5 SK2958 LCD DISPLAY AND KEYPAD FUNCTIONS There are two buttons on the front of the charger The scroll button is used to cycle through the information on the LCD screen The alarm reset button Can be pressed to clear alarm buzzer light and or display Can be held f...

Page 9: ... la bombanecesiteconectarseaunacajadeconexiónestancaalagua sepuede quitar el enchufe y empalmarla al cable de alimentación debidamente puesto a tierra Para mayor seguridad es posible que este circuito esté protegido con un interruptor con detección de falla a tierra La instalación completa debe cumplir el Código Eléctrico Nacional y todos los códigos y disposiciones locales pertinentes 6 PARA SU P...

Page 10: ...cerá garantía alguna por ningún material o producto que haya sido desarmado sin aprobación previa del Fabricante o que haya sido sometido a uso indebido aplicación indebida negligencia alteración accidente o acto de naturaleza que no haya sido instalado usado o mantenido según las instrucciones de instalación del Fabricante que haya sido expuesto a sustancias foráneas que incluyen pero no se limit...

Page 11: ... el contenedor para agua debe quedar limpio y sin residuos 8 La válvula de paso o la válvula de bola deben ser suministradas por el instalador e instaladas de acuerdo con todos los códigos 9 Se requieren sellos estancos al gas que retengan los gases y olores 10 Ventile los gases y olores hacia la atmósfera a través de una tubería de ventilación 11 Instale el soporte de la bomba Zoeller modelo 10 2...

Page 12: ...EBE ESTAR VISIBLE INTERRUPTOR DE FLOTADOR BOMBA CC M73 BOMBA PRINCIPAL ABRAZADERA INSTALACIÓN NORMAL VISTA EN DESPIECE DEL SISTEMA DE LA BOMBA FIGURA 1 R R BOMBA DE CC CONECTADA EN LÍNEA CON BOMBA SUMERGIBLE CAJA DE BATERÍA IMPORTANTE EL NIVEL DE APAGADO DEL CONJUNTO DE FLOTADOR DEBE ESTAR A UN MIN DE 2 5 CM 1 PULG POR ENCIMA DEL CENTRO DE LA T VEA LA NOTA DE INSTALACIÓN 3 VERIFIQUE QUE EL ORIFICI...

Page 13: ... conveniente el cargador de control puede ajustarse en un estante o repisa que esté cerca El cargador de control debe estar situado a 0 9 o 1 2 m 3 o 4 pies por encima del sumidero 5 Conecte el cable verde del sensor al conector del sensor figura 3 6 Conecte los cables del cargador de control a los terminales de la batería El cable blanco pos al terminal positivo y el cable negro ARRANQUE INICIAL ...

Page 14: ... con todos los códigos eléctricos y de instalación sanitaria aplicables incluyendo pero sin limitarse al Código Eléctrico Nacional los códigos locales regionales y o los códigos estatales de instalación sanitaria etc No se debe usar las instalaciones en lugares peligrosos No está diseñada para uso en lugares peligrosos SK2501 CAJA DE BATERIA BATERÍA MARINA DE 12 V PROVISTA POR EL USUARIO FIG 5 BOM...

Page 15: ...orriente de 115 V y desconecte el cable negro negativo del cargador de la batería Compruebe la batería Reemplace el motor si es necesario Vuelva a conectar y consulte el paso Instalación paso 7 9 La alarma no suena cuando la bomba está en funcionamiento a La bomba tiene que estar en funcionamiento durante 1 o más segundos antes de que suene la alarma b Asegúrese de que alarma no haya sido silencia...

Page 16: ...BAJA ALARMA DESACTIVADA CONTACTOS DE LAALARMA CABLE VERDE AL INTERRUPTOR DE FLOTADOR CABLE NEGRO CABLE BLANCO FIGURA 4 SK2503 FIGURA 5 SK2958 PANTALLA LCD Y FUNCIONES DEL TECLADO Hay dos botones en la parte frontal del cargador El botón de desplazamiento se utiliza para desplazarse por la información en la pantalla LCD El botón de reinicio de la alarma Puede ser presionado para silenciar el timbre...

Page 17: ...A BROCHE DE MISE À TERRE La fiche à 3 broches doit être insérée dans une prise à 3 broches mise à la terre Si l installation ne comprend pas de prise il faut la changer pour le type approprié la câbler et la mettre à la terre en conformité avec le code national de l électricité ainsi que tous les codes et règlements locaux applicables 7 Risqued électrocution Nepasenleverlecordond alimentationniled...

Page 18: ...Il faut utiliser une batterie à décharge poussée B C I de taille 27 avec une réserve de 175 minutes ou de plus grande capacité IL NE FAUT PAS utiliser de batterie sans entretien sauf si elle est du type à électrolyte gélifié ou de type AGM Il faut remplacer la batterie tous les trois ans Il ne faut pas permettre l accumulation de corrosion sur les bornes de la batterie Il ne faut pas mettre la bat...

Page 19: ...nstaller and installed according to any and all codes 9 Gas tight seals required to contain gases and odors 10 Des joints étanches aux gaz sont nécessaires pour contenir les gaz et les odeurs 11 Installer le pied de pompe Zoeller modèle 10 2421 sous la pompe pour fournir une cuve de décantation INSTALLATION RECOMMANDÉE POUR TOUTES APPLICATIONS CONSEILS POUR L INSTALLATION D UNE POMPE DE PUISARD 1 ...

Page 20: ... ÉVENT DOIT ÊTRE VISIBLE INTERRUPTEUR À FLOTTEUR POMPE C C POMPE PRINCIPALE M73 COLLIER INSTALLATION TYPIQUE VUE EXPLOSÉE DE LA POMPE FIGURE 1 R R IMPORTANT LE NIVEAU D ARRÊT DU FLOTTEUR DOIT ÊTRE À 2 5 CM 1 PO AU MINIMUM AU DESSUS DU CENTRE DU TÉ VOIR LE POINT 3 DE L INSTALLATION S ASSURER QUE LE TROU D ÉVENT EST VISIBLE VOIR LES INDICATIONS D INSTALLATION DE LA POMPE CLAPET ANTIRETOUR TROU D ÉVA...

Page 21: ... 3 et 4 pi au dessus du puisard 5 Raccorder le fil vert du capteur au raccordement du capteur figure 3 6 Brancher les fils du chargeur aux bornes de la batterie Le fil positif blanc à la borne positive et le fil négatif noir à la borne négative de la batterie Lorsque la connexion est bonne une alarme de test retentit DÉMARRAGE INITIAL ET FONCTIONNEMENT 1 Tester l installation à la recherche de fui...

Page 22: ...allations doivent être conformes aux codes électriques et de plomberie applicables y compris mais pas limité aux codes électriques nationaux locaux régionaux et aux codes de plomberie provinciaux Pas conçu pour utilisation dans les endroits dangereux SK2501 FIGURE 3 Copyright 2016 Zoeller Co Tous droits réservés BOÎTIER DE LA BATTERIE 12 V BATTERIE MARINE FOURNIE PAR L UTILISATEUR POMPE DE SECOURS...

Page 23: ...e la prise murale 115 V puis débrancher le fil noir du chargeur sur la borne négative de la batterie Vérifier la batterie La remplacer si nécessaire Rebrancher et se référer à l installation étape 7 9 L alarme ne sonne pas lorsque la pompe fonctionne a La pompe doit fonctionner pendant au moins une seconde avant que l alarme ne sonne b S assurer que l alarme n est pas en mode silencieux Appuyer et...

Page 24: ...orsque le flotteur l est aussi L alarme est retardée afin de réduire les nuisances sonores Le voyant jaune alarme désactivée indique que l alarme est actuellement en mode silencieux DÉTECTEURS DE MONOXYDE DE CARBONE Que vous ayez une pompe de secours Basement Sentry ou d une marque concurrente toutes les batteries produisent des sous produits gazeux lorsqu elles sont en charge Certains de ces sous...

Reviews: