SIP-2
38/145
USER GUIDE - Rev. 3 (January 2018)
5
CONFIGURATION AND MANAGEMENT
Configuration and management of the SIP-2 is performed through the console and through
access to the equipment HTML pages.
All the parameters controlling the equipment operation are described below in detail, using
the real HTML pages as an auxiliary graph example.
HTML page tree menu is shown in FIGURE 18.
Whenever changes are made, regardless of whether they are made through the console
or the HTTP server, the equipment must be informed what is to be done with them.
There are two options:
- the first is to execute the
Apply
command, which entails the immediate use of the
changes made.
- the second is to execute the
Save
command, which means that the changes will be
operative once the equipment is rebooted.
If accessing through the HTTP server, after making the changes and before executing
Apply
or
Save
, the
Send
button must be pushed to allow the equipment to obtain the
new desired values.
If executing the
Apply
command, if the changes are required to be permanent, the
Save
command must also be executed.
The only exceptions are changes affecting the SNMP configuration. Changes made to
the SNMP agent configuration will
only
be active after
RESETTING
the equipment. The
Apply
command is not sufficient, and so the changes must previously be saved using
the
Save
command before requesting the re-initialisation.