Zip Commercial HydroTap 86682 Installation And Operating Instructions Manual Download Page 9

Hydro Tap Installation and Operating Instructions - 86682 - March 2012 v1.05                                        Page 9 of 20

- The rear of the unit is fitted with, 1/4” John Guest, inlet and outlet fittings, 
specifically for the Zip high performance filter kit. 

- These instructions must be read in conjunction with the filter fitting 
instructions supplied with the high performance filter kit.

- The filter assembly must be located close to the appliance with sufficient 
space for service access. Consult the instructions supplied with the filter kit. 

To fit the external filter kit:

 

- Access the filter bypass valve, by removing the white plastic plug, located on 
the Left hand side of the undersink unit (see Fig.5)

- Using a suitable set of pliers, close the filter bypass valve as instructed in 
Figure 1.

- Remove the Inlet and Outlet plugs from the John Guest fittings as shown in 
Figures 2 ; 3 and 4.

- After suitably mounting the filter assembly to an adjacent surface, measure 
and trim the filter inlet and filter outlet tubes.

- Fit the tubes to their respective inlets and outlets, checking to ensure the flow 
of water corresponds to the direction indicated by the arrow on the filter head 
and by the instructions listed on the rear panel of the under sink unit.

- Check the lower left hand John Guest fitting is the ‘Inlet from the external 
filter’, and the right hand John Guest fitting is the ‘Outlet to the external filter’.

- Refit the white plastic plug and relocate the undersink unit, ensuring all air 
gaps and clearances are maintained. (see P4 Airflow details). 

- Activate the filter programme within the service mode. 

After Testing and Commissioning (Step F)

- Set the external filter life - Max 3000 Litres

- Set external filter use (No need to flush the external filter)

- Check all connections for leaks

 

Installation Procedure 

continued

Inlet from external filter 
with plug removed

Outlet to external filter 
with plug removed

Inlet with plug

Outlet with plug

John Guest fittings: Insertion and removal

Accessing the filter bypass valve

Fig.1

Fig.2

Fig.3

Fig.4

Fig.5

Summary of Contents for Commercial HydroTap 86682

Page 1: ...ge 1 of 20 Commercial HydroTap Filtered boiling and chilled drinking water for Commercial kitchens and tea rooms Installation and Operating Instructions This Installation Instruction covers the follow...

Page 2: ...r counter cupboard supporting the appliance is adequate for the total weight of the appliance when full of water Before Commissioning 1 Check the unit has been installed correctly 2 Check all plumbing...

Page 3: ...adjustment 11 Font Installation Procedure 12 Operating the Tap 13 Child Safety lock 14 Cleaning 14 Setting the Energy Saver Timer 15 Auxiliary Fan Attachment 16 Boiling Water Isolation 16 Set the Hot...

Page 4: ...ake care when lifting the Zip HydroTap undersink unit Some units may exceed safe lifting guidelines If you feel this is beyond your personal capabilities please seek assistance with the lift The weigh...

Page 5: ...ce Provider Frost Protection If this appliance is located where the ambient air temperature could fall below 5 C when the heater is not in use do not turn off the appliance electrically This safeguard...

Page 6: ...ace in the cupboard to install the undersink unit in accordance with these Installation Instructions A table of dimensions is given above NOTE Add 65mm to the Depth of the undersink unit to allow for...

Page 7: ...et on the unit For BC120 60 model connect the plastic inlet hose supplied to the cold water inlet on the unit This is located at the rear of the unit Position the Zip HydroTap undersink unit as close...

Page 8: ...ow if required Only choke the flow if it is excessively strong Model B boiling only models Measure and trim the red marked tube and connect it to the hot water outlet on the top of the undersink unit...

Page 9: ...jacent surface measure and trim the filter inlet and filter outlet tubes Fit the tubes to their respective inlets and outlets checking to ensure the flow of water corresponds to the direction indicate...

Page 10: ...ane Press the adjust button again to stop the Filter Flush Mode Turn OFF the Filter Flush stop cock and re locate the tube and stop cock in the filter compartment Turning OFF the Filter Flush Mode put...

Page 11: ...it will show the following Hot Temp Lvl Cold Temp Lvl NOTE The temperatures shown are actual not the set temperatures To revert back to the Normal Operation screen press the adjust buttons together ag...

Page 12: ...ixing nut with the Tube Spanner provided in the kit 6 Tighten the securing pin so the Font base is flush with the bench top NOTE The fixing nut above the drain elbow can be loosened to correctly posit...

Page 13: ...thin its normal specified lifespan Filter Change Light Flashing slowly The light will flash slowly when the filter is due for replacement and the LCD will show Filter Change Refer to Replacing the fil...

Page 14: ...ly Safety Lock boiling only models To activate the safety lock go to the LCD display using menu or buttons scroll to the Safety Lock display To turn ON adjust button to turn OFF adjust button After ab...

Page 15: ...Activating Sleep Mode This mode allows the HydroTap to go into Energy Saving mode In this mode the unit will go to sleep after a predetermined period of inactivity Press either Menu or Menu button unt...

Page 16: ...mode is active 5 To temporarily de actvate and dispense boiling water press the Safety Lock 3 three times rapidly the LED s will scroll from right to left 3 three times This operation confirms de act...

Page 17: ...f this isolates the water supply 2 Open the left door or on the compact model remove the front cover 3 Relieve system pressure via the filter flush stop cock a quick open and close will do 4 Grasp fil...

Page 18: ...ion Check water supply is on Check to ensure plumbing connection is made Check power plug is correctly fitted and switch is turned on Check for loom connection Contact local Zip Service Provider Check...

Page 19: ...Hydro Tap Installation and Operating Instructions 86682 March 2012 v1 05 Page 19 of 20 Typical undersink layout 50 50 Fused Spur...

Page 20: ...urned for repair to Zip or its Distributor This warranty does not cover damage resulting from non operation of the appliance the use of non authorised parts or consequential damage to any other goods...

Reviews: