Square TMD-Display
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
96
1 Byte
I
C - - W -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
-
-
[Disp] [X2] (Climate) Mode - Extended
Mode icon is shown
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
-
-
[Disp] [X2] Fan
2 levels: Min. (0% - 50%); Max. (51% - 100%)
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
-
-
[Disp] [X2] Fan
3 levels: Min. (0% - 33%); Med. (34% - 66%); Max.
(67% - 100%)
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
-
-
[Disp] [X2] Fan
Off/Auto + 1 level: Off/Auto = 0%; Max. (1% - 100%)
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
-
-
[Disp] [X2] Fan
Off/Auto + 2 levels: Off/Auto = 0%; Min. (1% - 50%);
Max. (51% - 100%)
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
-
-
[Disp] [X2] Fan
Off/Auto + 3 levels: Off/Auto = 0%; Min. (1% - 33%);
Med. (34% - 66%); Max. (67% - 100%)
95, 111,
127,
143
2 Byte
I
C - - W -
DPT_Value_2_Ucount
0 - 65535
-
-
[Disp] [X2] Number - Counter (2-bytes unsigned)
Object numeric value is shown
2 Byte
I
C - - W -
DPT_Value_2_Count
-32768 - 32767
-
-
[Disp] [X2] Number - Counter (2-bytes signed)
Object numeric value is shown
2 Byte
I
C - - W -
9.xxx
-671088.64 -
670760.96
-
-
[Disp] [X2] Number - Float (2-bytes)
Object numeric value is shown
2 Byte
I
C - - W -
DPT_Value_Temp
-273.0 - 670760.0
-
-
[Disp] [X2] (Climate) Temperature
Object value is shown (-99ºC to 199ºC)
96, 112,
128,
144
4 Byte
I
C - - W -
DPT_Value_4_Ucount
-2147483648 -
2147483647
-
-
[Disp] [X2] Number - Counter (4-bytes unsigned)
Object numeric value is shown
97, 113,
129,
145
14 Byte
I
C - - W -
DPT_String_8859_1
-
-
[Disp] [X2] Text from object
Received text is shown
98, 114,
130,
146
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
-
-
[Disp] [X2] (Climate) On/Off - Mode
0 = Cool; 1 = Heat. (Mode icon is shown when On/Off =
1, and Status = 0)
99, 115,
131,
147
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Disp] [X2] (Climate) On/Off - Status
0 = Halted; 1 = Running. (Status icon is shown when
On/Off = 1, and Status = 1)
148
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
-
-
[Thermostat] Scene Input
Scene Value
149
2 Byte
I
C - - W -
DPT_Value_Temp
-273.0 - 670760.0
25.0
-
[T1] Temperature Source 1
External Sensor Temperature
150
2 Byte
I
C - - W -
DPT_Value_Temp
-273.0 - 670760.0
-
-
[T1] Temperature Source 2
External Sensor Temperature
151
2 Byte
O
C T R - -
DPT_Value_Temp
-273.0 - 670760.0
-
√
-
[T1] Effective Temperature
Effective Control Temperature
152
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
-
√
-
[T1] Special Mode
1-byte HVAC Mode
153
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
√
-
[T1] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
√
-
[T1] Special Mode: comfort
0 = Off; 1 = On
154
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
√
-
[T1] Special Mode: standby
0 = Nothing; 1 = Trigger