Touch-MyDesign
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
47
Number
Size
I/O
Flags
Data Type (DPT)
Functional Range
1st boot
P
Reboot
P Name
Function
2 Bytes
I/O
C T R W U
9.xxx
-20.00 - 95.00
-
-
[Zx] 2-byte value (float)
-20 -95
1 Byte
I/O
C T R W U
DPT_Value_1_Ucount
0 - 255
-
-
[Zx] 1-byte value (unsigned int)
0-255
52
1 Byte
I
C - - W -
DPT_SceneNumber
0 - 63
-
-
[General] Scene: receive
0-63 (Run Scene 1-64)
53
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
-
-
[General] Scene: send
0-63 (Run or Save Scene 1-64)
54
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] LEDs: normal mode
1=Normal Mode; 0=No Action
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] LEDs: normal mode
0=Normal Mode; 1=No Action
55
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] LEDs: night mode
1=Night Mode; 0=No Action
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] LEDs: night mode
0=Night Mode; 1=No Action
56
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Touch Lock
0=Lock; 1=Nothing
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Touch Lock
1=Lock; 0=Nothing
57
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Touch Unlock
0=Unlock; 1=Nothing
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Touch Unlock
1=Unlock; 0=Nothing
58
1 Bit
C T - - -
DPT_Switch
0/1
-
-
[General] Welcome Back Object
1-bit generic control
59
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Flash LEDs
1=Flash LEDs; 0=No Action
60
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[General] Buzzer
1=Beep; 0=Nothing
61
1 Bit
I
C - - W -
DPT_Enable
0/1
-
√
-
[General] Buzzer Enabling
1=Enabled; 0=Disabled
62
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[T] Temperature Source 1
External Sensor Measure
63
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[T] Temperature Source 2
External Sensor Measure
64
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4= Protection
-
-
[T] Special Mode
1-byte HVAC Mode
65
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[T] Special Mode: comfort
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[T] Special Mode: comfort
0=Off; 1=On
66
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[T] Special Mode: standby
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[T] Special Mode: standby
0=Off; 1=On
67
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[T] Special Mode: economy
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[T] Special Mode: economy
0=Off; 1=On
68
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[T] Special Mode: protection
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[T] Special Mode: protection
0=Off; 1=On
69
1 Bit
I
C - - W -
DPT_Window_Door
0/1
-
-
[T] Window Status (input)
0=Closed; 1=Open
70
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[T] Comfort Prolongation
0=Nothing; 1=Timed Comfort
71
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4= Protection
- (W)
√
- (W)
[T] Special Mode Status
1-byte HVAC Mode
72
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[T] Setpoint
Thermostat setpoint input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[T] Basic Setpoint
Reference setpoint
73
1 Bit
I
C - - W -
DPT_Step
0/1
-
-
[T] Setpoint Step
0=-0.5°C; 1=+0.5°C
74
2 Bytes
I
C - - W -
DPT_Value_Tempd
-671088.64 -
670760.96
-
-
[T] Setpoint Offset
Float offset value