Touch-MyDesign
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
44
ANNEX I: COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular
meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
“
1st boot
” shows the cases where an object is assigned a certain value by the application program after a device download or a full reset. In case the value of such
assignment can be parameterised,
√
is shown in column “
P
”. Objects showing a hyphen (-) are not assigned a particular value and therefore can be assumed to be
initialised with the value “0” or with the corresponding updated value in case they depend on an external element (sensors, etc.). Moreover, if the object is sent (or is there
an option to send it) to the bus (write or read requests) after a download or a device reset from ETS, the marks
(W)
or
(R)
will be shown, respectively for transmissions or
read requests.
“
Reboot
” shows the cases where an object is assigned a certain value by the application program after a bus power failure. In case the value of such assignment can be
parameterised,
√
is shown in column “
P
”. Objects showing a hyphen (-) are not assigned a particular value and therefore can be assumed to maintain their previous value
after the failure or with the corresponding updated value in case they depend on external elements (sensors, etc.). Moreover, if the object is sent (or is there an option to
send it) to the bus (write or read requests) after a bus failure, the marks
(W)
or
(R)
will be shown, respectively for transmissions or read requests.
Number
Size
I/O
Flags
Data Type (DPT)
Functional Range
1st boot
P
Reboot
P Name
Function
0, 8, 16, 24
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X1] Binary Control: "0"
1-bit generic control
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[X1] Binary Control, Hold: "0"
1-bit generic control
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X] Binary Control
1-bit generic control
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X] Light On/Off
0=Off; 1=On
1 Bit
O
C T R - -
DPT_UpDown
0/1
-
-
[X] Move Shutter
0=Up; 1=Down
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X1] Light On/Off (Toggle)
0=Off; 1=On
1 Bit
O
C T R - -
DPT_UpDown
0/1
-
-
[X1] Move Shutter (Toggle Dir.)
0=Up; 1=Down
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X1] Binary Control: "1"
1-bit generic control
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[X1] Binary Control, Hold: "1"
1-bit generic control
1 Bit
I/O
C T R W U
DPT_Switch
0/1
-
-
[X1] Binary Control: Toggle "0/1"
1-bit generic control
1, 9, 17, 25
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[X1] Binary Control, Release: "0"
1-bit generic control
1 Bit
O
C T R - -
DPT_Step
0/1
-
-
[X] Stop Shutter / Step
0=Stop Shutter / Step Up; 1=Stop Shutter / Step Down
1 Bit
O
C T R - -
DPT_Step
0/1
-
-
[X1] Stop Shutter / Step (Toggle Dir.)
0=Stop Shutter / Step Up; 1=Stop Shutter / Step Down
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[X1] Binary Control, Release: "1"
1-bit generic control
2, 10, 18, 26
4 Bit
O
C T R - -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec.by 100%)
0x2 (Dec.by 50%)
-
-
[X] Light Dimming
4-bit dimming control