Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 21
P62 Under Torque Level:
Adjust to the desired trip threshold, as a
percentage of nominal torque.
Range:
10 – 100%
Default: 10%
To save changes
To exit without saving
P63 Under Torque Delay:
Adjust to set the time period that the torque
must fall below the threshold before a trip
occurs.
Range:
1 - 90 seconds
Default: 10 s
To save changes
To exit without saving
P70 Over Torque (Electronic Shear Pin):
Electronic Shear Pin or protection against over
torque. This protection is not active during the
accel & decel period.
To enter submenu to modify
To exit sub menu
P71 Over Torque Alarm:
Provide protection against excess torque. This
protection is not active during the accel & decel
period.
Range:
off; trip
Default: off
To save changes
To exit without saving
P72 Over Torque Level:
Adjust to the desired trip threshold, as a
percentage of nominal torque.
Range:
80 – 250%
Default: 100%
To save changes
To exit without saving
P73 Over Torque Delay:
Adjust to set the time period that the torque
must exceed the threshold before a trip occurs.
Range:
0 - 30 seconds
Default: 10 s
To save changes
To exit without saving
I10 DigIn 1 Mode
Activates digital input 1.
Range:
Enable; Invert; Disable
Default:
Enable
To save changes
To exit without saving
I11 DigIn 1 Variable
Set the functionality of digital input 1.
Range:
ESO; Remote trip; Remote reset
Default: Remote Reset
To save changes
To exit without saving
I12 DigIn 1 Delay
Set the delay that the digital input needs to be
active for the Soft starter to respond.
Range:
0.0 – 30.0 seconds
Default: 3.0
To save changes
To exit without saving
I20 DigIn 2 Mode
Activates digital input 2.
Range:
Enable; Invert; Disable
Default:
Disable
To save changes
To exit without saving
I21 DigIn 2 Variable
Set the functionality of digital input 2.
Range:
ESO; Remote trip; Remote reset
Default: Disabled
To save changes
To exit without saving
Setup Menu
5 Inputs
Status
Level
Delay
P70 Over Torque
Trip
100% 5s