Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 17
M01 Motor Amps:
Adjust to the value of motor full load current
(FLC) indicated on the motor rating plate, even if
connected in 6 wire (inside delta).
Range:
40% to maximum unit rating
Default:
Maximum rating of unit
To save changes
To exit without saving
M02 Motor Volts:
Adjust the value to the motor nameplate voltage.
Range:
199 – 481V
Default:
415V
To save changes
To exit without saving
M03 Motor PF:
Adjust to the value to the motor Power Factor as
indicated on the motor rating plate.
Range:
0.60 – 0.98
Default:
0.90
To save changes
To exit without saving
M04 Motor Wiring: (select models only)
Select the wiring configuration of the soft starter.
Range:
3 Wire; Std 6 Wire; Alt 6 Wire
Default:
3 Wire
To save changes
To exit without saving
C01 Run Mode:
Set to the configuration of the Smartstart 6000.
Range:
Bypass; Continuous
Default: Bypass
To save changes
To exit without saving
C02 Current Limit:
The current limit is expressed as a percentage of
the entered motor Amps (FLC). This current limit
setting operates during the ramp time only and
will over-ride the torque settings. Reducing the
current limit will limit the torque available to the
motor and load. If set too low it may prevent the
motor from accelerating or reaching full speed.
Range:
150 to 450% FLC
Default:
450%
To save changes
To exit without saving
Appendix A – Page 35 provides a guide to starting
parameters for various load types.
C10 Accel Ramp:
To enter submenu to modify
To exit sub menu
C11 Accel Time:
Adjust this to vary the time taken to ramp the
voltage to full supply voltage or the torque to
reach the ‘finish torque’. The accel time will
affect the actual current during starting – the
faster the rate of acceleration the higher the
start current.
Range:
1 to 60 seconds
Default: 10 s
To save changes
To exit without saving
C12 Start Torque:
The initial torque provided when a start is
initiated. Adjust to the lowest setting which
allows the motor to turn on a start command.
This is entered as a percentage of nominal
Torque (FLT). This setting will be dependent on
the torque required by the load.
Range:
15% to 200%
Default: 30%
To save changes
To exit without saving
Setup Menu
2 Motor
Setup Menu
3 Control
C10 Accel Ramp
10s
30%
130%
Accel Time
Start Torque
Final Torque