Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 19
P10 Acc Overtime :
To enter submenu to modify
To exit sub menu
P11 Overtime Alarm:
Protection against the start time exceeding the
preset acceleration or ramp time.
Range:
off; trip
Default: off
To save changes
To exit without saving
P12 Overtime Del:
The time exceeding the set ramp time before a
trip on Accel overtime occurs.
Range:
5 – 300 secs
Default: 120s
To save changes
To exit without saving
P20 Volt Imbal :
To enter submenu to modify
To exit sub menu
P21 Volt Imbal Alarm:
Provide protection against a supply voltage
imbalance.
Range:
off; trip
Default: trip
To save changes
To exit without saving
P22 Volt Imbal Level:
Adjust to set the voltage imbalance threshold, as
a percentage of the average phase voltage.
Range:
5 – 25%
Default: 25%
To save changes
To exit without saving
P23 Volt Imbal Delay:
Adjust to set a delay for the voltage imbalance
trip.
Range:
0– 5 seconds
Default: 5 s
To save changes
To exit without saving
P30 Curr Imbal:
To enter submenu to modify
To exit sub menu
P31 Curr Imbal Alarm:
Protection against a current imbalance.
Range:
off; trip
Default: trip
To save changes
To exit without saving
P32 Curr Imbal Level:
Set the current imbalance threshold, as a
percentage of the average phase current.
Range:
5 – 25%
Default: 25%
To save changes
To exit without saving
P33 Curr Imbal Delay:
Set a delay for the current imbalance trip.
Range:
0 – 10 seconds
Default: 10s
To save changes
To exit without saving
Status
Level
Delay
P20 Volt Imbal
Trip
25%
5s
Status
Level
Delay
P30 Curr Imbal
Trip
25%
10s
Trip/off
OverTime Delay
P10 Accel OverTime
Trip
120s