Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 25
To clear/reset any of the following a confirmation
code is required:
1 Reset Trip
2 Clr Mtr OL
3 Clr Counters
4 Clr Meters
5 Reset Config
11 Clr Stress
12 Clr All Data
13 Factory Reset
The Confirmation Code is: 1470
This menu provides indication of inputs and wiring
checks.
Each Relay can also be forced on and the Analogue
output set for 100%.
S1 Digital In:
0 = No control signal present
1 = Control signal present
S2 Thermistor In:
Displays thermistor resistance in Kohms.
The trip resistance is 3000Ohms and a short circuit is
detected when <20Ohms.
S3 Chk Motor Wirirng:
Displays detected motor wiring.
Example: ‘ Correct Mtr 3 wire ‘
S4 Chk CT1/CT2
Displays detected CT connection.
Example: ‘Correct +L1 / +L3’
Setup Menu
9 Commands
Setup Menu
10 Starter Diag
S1 Digital In
EN=0
D1=0
D2=0
Enable Input
Digital 1 Input
Digital 2 Input