Programming
Technical Manual: Smartstart
®
6000
IMI0042 rev D
Page 14
Local Control Panel / Remote Console
The local control panel consists of 5 push buttons and
a plain English display to simplify programming.
Increase the value or change selection.
Navigate up through menu / submenus.
Decrease the value or change selection.
Navigate down through menu / submenus.
Allows access to menu, submenus & saves
the parameter entered.
Escapes from current menu position
without saving.
Manual reset of a trip (if enabled).
Operating Status Indication
‘Off’
The Smartstart
®
has control power applied but not
enabled.
‘Standby’
The Smartstart
®
has been enabled to start and the run
relay energized to bring in the line contactor (if
installed). The Smartstart
®
will initiate a start
immediately 3 phase supply is applied. Supply Voltage
is displayed.
‘Accel’
The Smartstart
®
is accelerating the motor. Ramp time
completed (%) & Motor Current (A) displayed
‘At Speed’
The motor is at full speed, the accel time period may
not be complete. Ramp time completed (%) & Motor
Current (A) is displayed.
‘Run Bypass or Cont.’
The ramp time is complete
and the bypass contactor operated or SCR’s are in full
conduction. Motor Current (A) is displayed.
‘Decel’
The Smartstart
®
is decelerating the motor. Ramp time
completed (%) & Motor Current (A) is displayed.
The Menu Map (Dash Board)
This symbol identifies the parameters for quick
setup.
Off
0A
0%
Status / Fault displayed in
Plain English
Supply Voltage and
Motor Current
Bargraph Value
Default ‘Motor current %’
Bar Graph to provide
visual indication
ENTER
SMARTSTART 6000
6R030
r1.XX
140 SCR % Thermal
121 Mtr Capacity
415v
50Hz
100A
1-2-3
56kW
90% Torq
0.9PF
90% Pwr
56kW
Volt Imbal
0%
415
415
415V
Curr Imbal
0%
100
100
100A
0 Starts
0 Trip
0.8 RunHrs
400kw.Hrs
Last Trip
Esc
Main Menu
Ready
100A
80%
Note 1.:
The default screen can be
changed. See menu item
‘D02 Default Screen’.
Note 2.:
The bargraph Variable can
be changed. See menu
item ‘Bargraph var’.
Note 3.:
User Access to the menu
may be resticted. See
menu item ‘D01 Menu
Access’.