![background image](http://html1.mh-extra.com/html/zehnder-pumpen/kompaktboy-doppel/kompaktboy-doppel_operating-manual_3324126076.webp)
Kompaktboy Double
en
English
76
The sewage check valve, which is required according to pertinent regulations, has to be
mounted in the lifting unit Kompaktboy Double 3.0 in the form of two supplied ball check
valves in grey-cast iron.
i
5.5.2 Pressure line with the Kompaktboy 3.0
5.5.2.1 Putting on the ball check valves
Mounting of the left ball check valve is described in the following. Mounting of the right ball
check valve is carried out analogously.
1.
Z
Insert the supplied seal rings (O-Ring DN 100)
into the groove of the pressure outlet of the
collecting tank.
2.
Z
Insert the threaded bolt (M16x60) into hole 1
3.
Z
Put on the supplied ball check valve. While
doing so, arrange the holes/threaded hole
congruently.
4.
Z
Screw the nut (M16) on the threaded bolt 1.
5.
Z
Screw in the 3 screws M16x40 and
tighten the 4 screw connections equally cross-
wise.
Summary of Contents for KOMPAKTBOY DOPPEL
Page 21: ...Kompaktboy Doppel Deutsch 21 Einbaubeispiel zur Absch tzung des Platzbedarfs der Hebeanlage...
Page 44: ...Kompaktboy Doppel Deutsch 44 9 2 1 Abmessungen Kompakboy Doppel 1 1 und 1 5...
Page 45: ...Kompaktboy Doppel Deutsch 45 9 2 2 Abmessungen Kompakboy Doppel 3 0...
Page 46: ...Kompaktboy Doppel Deutsch 46 10 Ersatzteilliste...
Page 92: ...Kompaktboy Double en English 92 9 2 1 Dimensions of the Kompaktboy Double 1 1 and 1 5...
Page 93: ...Kompaktboy Double en English 93 9 2 2 Dimensions of the Kompaktboy Double 3 0...
Page 94: ...Kompaktboy Double en English 94 10 List of spare parts...
Page 140: ...Kompaktboy Double fr Fran ais 140 9 2 1 Dimensions Kompakboy Double 1 1 et 1 5...
Page 141: ...Kompaktboy Double fr Fran ais 141 9 2 2 Dimensions Kompakboy Double 3 0...
Page 142: ...Kompaktboy Double fr Fran ais 10 Liste de pi ces de rechange...