Page – 112/139
AFFZP0BB – ACE3 – User Manual
11)
RELOAD HM FROM MDI
Cause:
The hour-meter of the controller is transferred and recorded on the hour-meter
of the standard MDI.
12)
CHECK UP NEEDED
Cause:
This is a warning to point out that it is time for the programmed maintenance.
Troubleshooting:
Turn on the CHECK UP DONE option after that the maintenance service.
13)
PARAM TRANSFER
Cause:
Master uC is transferring parameters to the supervisor.
Troubleshooting:
Wait until the end of the procedure. If the alarm remains longer, re-cycle the
key.
14)
THROTTLE PROG.
Cause:
A wrong profile has been set in the throttle profile.
Troubleshooting:
Set properly the throttle-related parameters (see paragraph 8.8).
15)
INCORRECT START
Cause:
Incorrect starting sequence. Possible reasons for this alarm are:
-
A travel demand active at key-on.
-
Man-presence sensor active at key on.
Troubleshooting:
- Check
wirings.
-
Check microswitches for failures.
-
Through the TESTER function, check the state of the inputs are coherent
with microswitches states.
-
If the problem is not solved, replace the logic board.
16)
VACC OUT OF RANGE
Cause:
The CPOT input read by the microcontroller is not within the MIN VACC ÷ MAX
VACC range, programmed through the PROGRAMM VACC function (see
paragraph 8.1).
Summary of Contents for ACE3
Page 14: ...Page 14 139 AFFZP0BB ACE3 User Manual 3 2 Connection drawing ACE3 Traction Standard...
Page 15: ...AFFZP0BB ACE3 User Manual Page 15 139 3 3 Connection drawing ACE3 Traction Premium...
Page 16: ...Page 16 139 AFFZP0BB ACE3 User Manual 3 4 Connection drawing ACE3 Pump Standard...
Page 17: ...AFFZP0BB ACE3 User Manual Page 17 139 3 5 Connection drawing ACE3 Pump Premium...