10

  ____________________   

DIRECTION   switch   to   the   other   position   (Pic   20).      

Press   and   

HOLD

   the   

PROGRAM

   button   again   

and   ensure   that   the   door   movement   is   now   
correct.   Continue   holding   the   

PROGRAM

   button.   

When   the   door   reaches   the   fully   open   position,   
release   the   

PROGRAM

   button,   the   opening   light   

should   remain   lit   (Pic   21)   and   the   beeper   will   

sound   repeatedly   to   indicate   that   it   is   ready   to   
learn   the   distance   to   the   ground.   

     

   Pic   21   

   

Press   and   

HOLD

   the   

PROGRAM

   button   to   close   

the   door,   release   the   button   immediately   the   

door   reaches   the   ground.      If   the   door   stops   
before   the   ground,   release   the   

PROGRAM

   

button,   release   the   Manual   Override   Lever,   close   

the   door   to   the   ground   and   re-­‐engage   the   
Manual   Override   Lever.      Repeat   calibration   steps   

1

   and   

2

   and   if   the   door   will   still   not   reach   the   

fully   open   or   fully   closed   position   then   the   door   
may   be   out   of   balance   or   poorly   maintained   and   
should   be   serviced.   

3:

   Once   the   door   has   fully   opened   and   fully   

closed,   release   the   

PROGRAM

   button   and   press   

the   

illuminated

   Control   Box   button   (Pic   22).   

   

Pic   22   

   

If   there   are   no   safety   devices   fitted   then   this   
button   must   be   held   while   the   third   stage   of   the   
calibration   process   is   carried   out,   otherwise   it   
can   be   released   once   the   door   starts   to   open.   

The   door   should   automatically   open   fully,   wait   
and   then   close   fully.      During   this   process   it   will   
beep   repeatedly   and   the   Operator   Light   will   

flash   to   warn   that   the   Control   Head   is   learning   
the   force   profile   of   the   door.      Keep   clear   of   the   
door   and   wait   for   the   third   stage   to   end.   

4:

   Once   the   third   stage   of   the   calibration   process   

is   complete,   the   door   will   be   closed   and   the   
Operator   Light   will   be   lit   with   the   beeper   

sounding   once   every   5   seconds   to   indicate   entry   

into   diagnostic   mode.      The   door   can   now   be   
cycled   using   the   

illuminated

   Control   Box   button.      

During   the   diagnostic   runs,   the   door   balance   is   

indicated   by   the   brightness   of   the   Operator   
Light,   the   beeper   will   sound   if   a   track   irregularity   
is   detected,   and   the   beeper   will   sound   

repeatedly   if   the   belt   is   slipping   when   the   door   is   
at   the   fully   open   or   closed   position.      See   the   
fault   finding   section   on   page   11   for   further   

details.   

5:

   To   exit   the   diagnostic   mode,   press   and   release   

the   

PROGRAM

   button,   there   will   be   two   beeps   

to   indicate   that   the   calibration   is   completed.      

The   Operator   Light   will   fade   out   after   3   minutes.   
   

TESTING   THE   DOOR   OPERATION   

Once   calibration   is   complete   the   door   should   be   

cycled   normally   a   few   times   using   the   

illuminated

   Control   Box   button   to   ensure   

correct   operation,   the   door   must   reverse   when   

it   contacts   a   1.5”   high   object   (or   a   2”   by   4”   board   
laid   flat)   on   the   floor   (Pic   23).      See   pages   11   and   
12   to   adjust   the   reversing   decision   height,   the   

soft   start   duration,   the   closing   speed   change   
point   and   the   obstruction   tolerance   if   required.      

Finally   adjust   the   Manual   Override   Lever   

tension   now   that   the   V-­‐belt   has   bedded   in.

   

   

Pic   23   

   

There   is   an   automatic   close   facility   which   can   be   
enabled   by   turning   on   the   AUTOCLOSE   switch.      
The   factory   default   close   time   is   15   seconds;   
refer   to   the   programming   guide   to   alter   the   

time.      The   beeper   will   sound   and   the   Operator   
Light   will   flash   for   5   seconds   before   the   start   of   
the   automatic   close   to   warn   of   an   impending   

unattended   door   operation.   

Opening   

Closing   

Summary of Contents for 8825-R4

Page 1: ......

Page 2: ...fore installing the opener 4 Where possible install the door opener 7 feet or more above the floor Mount the emergency release 6 feet above the floor 5 Do not connect the opener to the source of power...

Page 3: ...e cela est possible installer l l ouvre porte 2 14m ou plus au dessus du sol Monter le d verrouillage d urgence 1 83m au dessus du sol 5 Ne pas brancher l ouvre porte la source d alimentation lectriqu...

Page 4: ...15 3 Install the Control Head Page 5 15 4 Fit the Manual Override Page 6 16 5 Fit the Control Box Page 6 16 6 Fit the optional Automatic Lock Page 7 17 7 Connect to the power supply Page 7 17 8 Insta...

Page 5: ...ing the operator 5 Fitting the Control Head 6 Fitting the Manual Override Lever 7 Fitting the Control Box 7 8 Fitting the optional Automatic Lock 8 Supply outlet information 8 Accessory wiring 8 Built...

Page 6: ...pending on the door position A significant advantage of the ZAP drive system with its soft start and its fast obstruction sensing is that when an object obstructs the door s travel the cables will pro...

Page 7: ...e the other end to the torque arm fixing hole on the Control Head use the supplied spacer if the offset is not enough to clear the drum Pic 5 Pic 5 Align the Control Head driven pulley s keyway with t...

Page 8: ...ecure the lever using the M5 screws and flange nuts supplied Pic 9 Pic 9 Place the hook in the cable D shackle or a convenient link of the chain and ensure that the lever is slightly above horizontal...

Page 9: ...d Pic 15 Pic 15 SUPPLY OUTLET A 115V 60Hz grounding type outlet is required for the 8825 R4 this should be installed by a qualified electrician in accordance with the local electrical codes within 4 o...

Page 10: ...AFETY and Pic 19 Note The supplied photo eyes are not polarity sensitive and can be wired either way around Pic 19 When the photo eyes are properly aligned the red safety light on the Control Box circ...

Page 11: ...rd stage to end 4 Once the third stage of the calibration process is complete the door will be closed and the Operator Light will be lit with the beeper sounding once every 5 seconds to indicate entry...

Page 12: ...obstruction A calibration reset pages 9 10 is required for a new setting to take effect Release the PROGRAM button after the fourth beep to program the closing speed change point 14 beeps representing...

Page 13: ...ILLUMINATED button after the first beep for vacation mode The light goes out and the radios and external inputs are all ignored until the button has been pressed again to leave vacation mode Release t...

Page 14: ...omatically opens REASON REMEDY A The V belt tension is too loose and the belt is slipping over the motor pulley Increase the tension by releasing the Manual Override Lever and screwing the hook in a f...

Page 15: ...e ZAP Controller has not been calibrated to this door Refer to the calibration process on pages 9 and 10 C The obstruction tolerance may be too low Refer to the Installer Programming instructions on p...