58
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
ELECTRICAL DATA
One
fi
eld provided power supply circuit to the unit.
Field con nec tions to fac to ry pro vid ed Non-Fused
Dis con nect Switch (Opt), or Ter mi nal Block (Opt).
Factory con nec tions to Terminal Blocks in each of the
two Pow er Pan els.
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION WITH FIELD SUPPLIED CIRCUIT
PROTECTION
Suitable for:
Y -
∆
Start and
Across-The-Line-Start
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION – 2 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the Chiller. Field connections to Factory Provided Terminal Block (Standard) or Non-Fused Disconnect (option).
No Internal Branch Circuit Protection (Breakers) per Motor Control Center
10
)
See page 62 for Electrical Data footnotes.
See page 62 for notes.
Technical Data
CHILLER FIELD-SUPPLIED WIRING
MODEL VOLTS FIELD PROVIDED POWER SUPPLY FACTORY PROVIDED (LUGS) WIRE RANGE
7
YCAS MIN NF OVER-CURRENT PROTECTION
13
STANDARD OPTIONAL NF
MCA
1
DISC SW
2, 9
MIN.
3, 5
MAX.
4, 6
TERMINAL BLOCK DISC. SWITCH
0130EC
460 273 400 300 350 # 1 - 500 (2) 3/0-250
575 217 250 250 300 # 1 - 500 # 6 - 350
0140EC
460 293 400 350 400 (2) # 2 - 300 (2) 3/0-250
575 234 250 300 300 # 1 - 500 # 6 - 350
0150EC
460 307 400 350 400 (2) # 2 - 300 (2) 3/0-250
575 246 400 300 300 # 1 - 500 (2) 3/0-250
0160EC
460 320 400 400 400 (2) # 2 - 300 (2) 3/0-250
575 257 400 300 350 # 1 - 500 (2) 3/0-250
0170EC
460 335 400 400 450 (2) # 2 - 300 (2) 3/0-250
575 268 400 300 350 # 1 - 500 (2) 3/0-250
0180EC
460 347 400 400 450 (2) # 2 - 300 (2) 3/0-250
575 277 400 350 350 (2) # 2 - 300 (2) 3/0-250
0200EC
460 375 400 450 500 (2) # 1 - 500 (2) 3/0-250
575 299 400 350 400 (2) # 2 - 300 (2) 3/0-250
0210EC
460 393 600 450 500 (2) # 1 - 500 (2) 250-500
575 313 400 350 400 (2) # 2 - 300 (2) 3/0-250
0230EC
460 407 600 450 500 (2) # 1 - 500 (2) 250-500
575 324 400 400 450 (2) # 2 - 300 (2) 3/0-250
LD05550
Summary of Contents for YCAS0130
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM1 204 5 This page intentionally left blank...
Page 47: ...47 YORK INTERNATIONAL FORM 201 19 NM1 204 6 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 19 NM1 204 This page intentionally left blank 7...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM1 204 LD09239 FIG 22B CONTROL PANEL COMPONENT LOCATION 7...
Page 75: ...75 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LEGEND LD09241...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM1 204 7 CONNECTION DIAGRAM SYSTEM WIRING LD09242...
Page 78: ...78 YORK INTERNATIONAL FORM 201 19 NM1 204 Technical Data COMPRESSOR TERMINAL BOX LD09243...
Page 79: ...79 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LD09373 ELEMENTARY DIAGRAM CONTROL CIRCUIT...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...
Page 121: ...121 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...