150
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
System Data:
The following sequence of three displays are provided
fi
rst for System 1, then for System 2, and then for Sys-
tems 3 and 4 as applicable.
This message indicates whether the compressor on this
system is ON or OFF.
This message indicates the compressor motor current in
amps and as a percentage of Full Load Amps.
This message indicates the system oil pressure, suction
pressure, and discharge pressure.
This message shows the system oil temperature, suction
temperature, and discharge temperature.
These messages indicate compressor suction gas satura-
tion temperature and superheat.
This message indicates compressor discharge gas satura-
tion temperature and superheat.
This message indicated the compressor slide valve po-
sition. 0 steps equals minimum capacity and 75 steps
equals fully loaded.
The upper message indicates the difference (error)
be tween actual leaving chilled liquid temperature and
the pro grammed Target temperature. The lower message
indicates the rate of change of the chilled liquid leaving
tem per a ture in degrees per minute. A minus sign (-)
in di cates falling temperature. No sign indicates rising
tem per a ture.
This message advises which system is programmed as
the lead.
This message indicates the position of the optional
aux il ia ry contacts for the evaporator water pump and
the status of the evaporator heater.
For the evaporator pump contacts, ON = contacts closed,
OFF = contacts open.
The Evaporator Heater status is controlled on ambient
temperature as follows: If measured ambient falls be low
40°F (4°C), the Evaporator Heater is switched ON. If
measured ambient then rises above 45°F (7°C) the heater
is switched OFF. The evaporator heater pre vents water
standing in the evaporator from freezing.
This message indicates that a remote device such as a
Remote Control Center, an ISN controller, or another
device sending a PWM signal for temperature or cur rent
reset is overriding control points programmed through
the keypad or default microprocessor set points. The
following displays may be encountered:
NONE – No remote control active. Remote
monitoring may be active.
ISN – YorkTalk via ISN or Remote Control
Center (remote mode).
PWM CURR – EMS PWM Current Limiting Enabled
PWM TEMP – EMS PWM Temp. Reset Enabled
CUR/TEMP – EMS PWM Current Limiting &
Temperature Reset Enabled
L E A D S Y S T E M I S
S Y S T E M N U M B E R #
E V A P P U M P I S O F F
E V A P H E A T E R I S O N
A C T I V E R E M O T E C T R L
N O N E
Micro Panel Contents
T E M P E R R O R 0 0 . 5
°
F
T E M P R A T E - 0 . 9 ° F / M
S Y S # C O M P R E S S O R
I S O N
S Y S # M O T O R C U R R E N T
1 3 5 A M P S 7 8 % F L A
S Y S # O I L = 1 7 5 P S I G
S P = 6 2 D P = 2 7 1 P S I G
S Y S # O I L = 1 5 4 . 8 ° F
S T = 3 9 . 0 D T = 1 2 3 . 7 ° F
S # S A T S U C T = 3 4 . 7 ° F
S U C T S H E A T = 1 0 . 5 ° F
S # S A T D S C H = 1 2 9 ° F
D S C H S H E A T = 6 2 . 8 ° F
S Y S # S V S T E P = 4 0
Summary of Contents for YCAS0130
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM1 204 5 This page intentionally left blank...
Page 47: ...47 YORK INTERNATIONAL FORM 201 19 NM1 204 6 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 19 NM1 204 This page intentionally left blank 7...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM1 204 LD09239 FIG 22B CONTROL PANEL COMPONENT LOCATION 7...
Page 75: ...75 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LEGEND LD09241...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM1 204 7 CONNECTION DIAGRAM SYSTEM WIRING LD09242...
Page 78: ...78 YORK INTERNATIONAL FORM 201 19 NM1 204 Technical Data COMPRESSOR TERMINAL BOX LD09243...
Page 79: ...79 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LD09373 ELEMENTARY DIAGRAM CONTROL CIRCUIT...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...
Page 121: ...121 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...
Page 193: ...193 YORK INTERNATIONAL FORM 201 19 NM1 204 8 This page intentionally left blank...