147
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
Closed:
Low Ambient Mode allows the Low Ambient Cut-Out
to be programmed from 0 to 50 °F (-18 to 10°C). Val ues
above 25°F (-4°C) can be used to automatically shut
down the chiller when direct cooling methods be come
operational.
SWITCH 3: Refrigerant
Open:
The R-407C Mode MUST be selected for models us ing
refrigerant R-407C. Incorrect selection of this switch
may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
SWITCH 4: Unit Type
Open:
DO NOT USE THIS POSITION.
Incorrect programming may cause
damage to the chiller.
Closed:
Place the switch in the CLOSED position selects the
type of chiller as an air cooled chiller (YCAS). The
switch MUST always be in the CLOSED position.
Incorrect programming may cause
damage to the chiller.
S 1 - 2 A M B I E N T C O N T R O L
L O W A M B I E N T
S 1 - 3 R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3 R E F R I G E R A N T
R - 2 2
Dip Switch Physical Location and Setting
FIG. 49
–
ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR BOARD
LD03511A
LD03511B
“OPEN” Position:
Left side of switch
pushed in
“CLOSED” Position:
Right side of switch
pushed in
8
S 1 - 4 Y C W S
S 1 - 4 Y C A S
SWITCH 5: Motor Current Average option
(start-up)
Open:
DO NOT USE THIS POSITION.
Nuisance trips at start-up could result.
S 1 - 5 M O T O R C U R R E N T
A V E R A G I N G E N A B L E D
028981-G
Summary of Contents for YCAS0130
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM1 204 5 This page intentionally left blank...
Page 47: ...47 YORK INTERNATIONAL FORM 201 19 NM1 204 6 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 19 NM1 204 This page intentionally left blank 7...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM1 204 LD09239 FIG 22B CONTROL PANEL COMPONENT LOCATION 7...
Page 75: ...75 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LEGEND LD09241...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM1 204 7 CONNECTION DIAGRAM SYSTEM WIRING LD09242...
Page 78: ...78 YORK INTERNATIONAL FORM 201 19 NM1 204 Technical Data COMPRESSOR TERMINAL BOX LD09243...
Page 79: ...79 YORK INTERNATIONAL FORM 201 19 NM1 204 7 LD09373 ELEMENTARY DIAGRAM CONTROL CIRCUIT...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...
Page 121: ...121 YORK INTERNATIONAL FORM 201 19 NM1 204 7 This page intentionally left blank...
Page 193: ...193 YORK INTERNATIONAL FORM 201 19 NM1 204 8 This page intentionally left blank...