Johnson Controls Unitary Products

Unit Controls:

a. Unit shall be complete with self-contained low-voltage 

control circuit protected by a resettable circuit breaker on 
the 24-volt transformer side.

b. Unit shall incorporate a lockout circuit which provides 

reset capability at the space thermostat or base unit 
should any of the following standard safety devices trip 
and shut off compressor:

c. Loss-of-charge/Low-pressure switch.

• High-pressure switch.

• Freeze-protection thermostat, evaporator coil. If any of 

the above safety devices trip, an LED (light-emitting 
diode) indicator shall flash a diagnostic code that 
indicates which safety switch has tripped.

d. Unit shall incorporate “AUTO RESET” compressor over 

temperature, over current protection.

e. Unit shall operate with conventional thermostat designs 

and have a low voltage terminal strip for easy hook-up. 

f. Unit control board shall have on-board diagnostics and 

fault code display.

g. Standard controls shall include anti-short cycle and low 

voltage protection, and permit cooling operation down to 
0 ºF.

h. Control board shall monitor each refrigerant safety switch 

independently.

i. Control board shall retain last 5 fault codes in non-

volatile memory, which will not be lost in the event of a 
power loss.

ELECTRIC HEATING SECTION (IF EQUIPPED)

An electric heating section, with nickel chromium elements, 
shall be provided in a range of 9 thru 54 KW, offering two states 
of capacity all sizes. The heating section shall have a primary 
limit control(s) (automatic reset) to prevent the heating element 
system from operating at an excessive temperature. The Heat-
ing Section assembly shall slide out of the unit for easy mainte-
nance and service. Units with Electric Heating Sections shall be 
wired for a single point power supply with branch circuit fusing 
(where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125 ºF outdoor 
temperature, exceeding maximum load criteria of AHRI Stan-
dard 340/360. The compressor, with standard controls, shall be 
capable of operation down to 0 ºF outdoor temperature.

ELECTRICAL REQUIREMENTS - 

All unit power wiring shall 

enter unit cabinet at a single factory provided location and be 
capable of side or bottom entry to minimize roof penetrations 
and avoid unit field modifications. Separate side and bottom 
openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

 - 

Compressor – 5 Years, 

Elect. Heat Elem. – 5 Years, Parts – 1 Year

FACTORY INSTALLED OPTIONAL OUTDOOR AIR

 (Shall be 

made available by either/or):

 

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER

 

– Outdoor and return air dampers that are interlocked and 
positioned by a fully-modulating, spring-return damper 
actuator. The maximum leakage rate for the outdoor air 
intake dampers shall not exceed 2% when dampers are 
fully closed and operating against a pressure differential 
of 0.5 IWG. A unit-mounted potentiometer shall be 
provided to adjust the outdoor and return air damper 
assembly to take in outdoor air to meet the minimum 
ventilation requirement of the conditioned space during 
normal operation. During economizer operation, a mixed-
air temperature control shall modulate the outdoor and 
return air damper assembly to prevent the supply air 
temperature from dropping below 55 ºF. Changeover from 
compressor to economizer operation shall be provided by 
an integral electronic enthalpy control that feeds input into 
the basic module. The outdoor intake opening shall be 
covered with a rain hood that matches the exterior of the 
unit. Water eliminator/filters shall be provided. 
Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss. 
Available with barometric relief or power exhaust.

MOTORIZED OUTDOOR AIR DAMPERS

 – Outdoor and 

return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The 
maximum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in the 
design CFM of outdoor air to meet the ventilation 
requirements of the conditioned space during normal 
operation. Whenever the indoor fan motor is energized, 
the dampers open up to one of two pre-selected positions 
– regardless of the outdoor air enthalpy. Dampers return 
to the fully closed position when the indoor fan motor is 
de-energized. Dampers shall fully close on power loss.

ADDITIONAL FACTORY INSTALLED OPTIONS

ALTERNATE INDOOR BLOWER MOTOR

 – For 

applications with high restrictions, units are available with 
optional indoor blower motors that provide higher static 
output and/or higher airflow.

CONVENIENCE OUTLET (POWERED/NON-POWERED)

– 

Unit can be provided with an optional 120VAC GFCI outlet 
with cover on the corner of the unit housing the compressors.

ELECTRIC HEAT

 - Electric Heaters range from 9 kW to 

54 kW and are available in all the voltage options of the 
base unit.

PHASE MONITOR

 - Designed to prevent damage in out-

of-phase condition.

COIL GUARD

 - Designed to prevent condenser coil 

damage.

BAS CONTROLS

 - Include supply air sensor, return air 

sensor, dirty filter indicator and air proving switch.

Summary of Contents for Predator XP Series

Page 1: ...s are self contained and assembled on rigid full perimeter base rails allowing for 3 way forklift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to...

Page 2: ...3 4 NPT Female Connection Belt drive blower motor Condenser section Filter drier solid core Filter access 2 or 4 filter options Disconnect location optional disconnect switch Compressor 2 Access High...

Page 3: ...ions 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S...

Page 4: ...rocating compressors Scroll compressors do not require crankcase heaters Phase Monitors are standard on units with scroll compressors This accessory monitors the incoming power to the unit and protect...

Page 5: ...or air As the outdoor air intake dampers open the return air dampers close The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input There...

Page 6: ...rrosion ElectroFin E coat Evaporator Coils The evaporator coils are coated with an epoxy polymer coating to protect against corrosion Control Options BAS Building Automation System Controls Simplicity...

Page 7: ...unit with a down flow economizer Power exhaust plugs into the connector in the unit bulkhead You must purchase 1EH0408 barometric relief when applying to a horizontal flow application Manual Outdoor A...

Page 8: ...Motorized Damper Horizontal Incl Hood Damper Filter no Barometric Relief 2EE04705924 Economizer Downflow Incl Barometric Relief All Hoods 2EE04706024 Economizer Horizontal Incl Dampers Hoods no Barom...

Page 9: ...nd be accessible through hinged access door Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without rem...

Page 10: ...ailable by either or ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER Outdoor and return air dampers that are interlocked and positioned by a fully modulating spring return damper actuator The maximum leakage...

Page 11: ...t available SMOKE DETECTOR A smoke detector can be factory mounted and wired in the supply and or return air compartments OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF CURB 14 and 8 high full perime...

Page 12: ...7 3 35 7 9 3 35 8 6 3 30 13 2 3 0 17 F capacity rating Mbh 43 0 51 0 53 0 58 0 90 0 System power KW COP 5 7 2 20 6 4 2 25 6 9 2 25 7 8 2 20 13 5 2 2 HSPF Btu Watts hr DIMENSIONS inches Length 89 89 89...

Page 13: ...1725 Frame size 56 56 56 56 56 56 56 56 56 184T FILTERS Quantity Size 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 3 4 24 x 20 x 4 3 4 24 x 2...

Page 14: ...121 3 4 9 90 6 76 7 62 9 49 1 111 6 5 5 88 1 74 1 60 1 46 1 67 111 3 4 9 111 3 93 3 79 5 65 6 51 8 101 6 5 5 101 6 89 9 75 9 61 9 47 9 62 99 9 4 8 99 9 99 9 97 3 83 5 69 6 55 8 92 3 5 4 92 3 92 3 91...

Page 15: ...6 67 3 8 6 67 3 64 1 53 0 41 8 30 7 62 68 8 7 8 68 8 68 8 66 5 55 1 43 7 32 3 61 6 8 6 61 6 61 6 61 1 49 9 38 8 27 6 57 70 6 7 7 70 6 70 6 67 2 55 8 44 4 33 0 65 0 8 5 65 0 65 0 61 6 50 4 39 3 28 1 2...

Page 16: ...64 0 50 0 113 1 6 5 88 6 74 7 60 8 46 9 67 112 3 5 7 112 3 97 9 83 9 69 9 55 9 103 5 6 5 103 5 94 5 80 6 66 7 52 8 62 106 2 5 6 106 2 106 2 106 2 92 2 78 2 64 2 96 4 6 4 96 4 96 4 96 4 82 5 68 6 54 7...

Page 17: ...9 68 7 10 0 68 7 68 7 58 2 47 1 36 0 62 72 5 9 0 72 5 72 5 73 8 62 5 51 2 39 9 65 9 9 9 65 9 65 9 65 9 57 6 46 6 35 5 57 72 0 9 0 72 0 72 0 74 4 63 1 51 8 40 5 65 2 9 9 65 2 65 2 65 2 57 1 46 0 34 9...

Page 18: ...8 74 9 58 1 128 6 7 1 106 2 89 0 71 8 54 5 67 127 2 6 2 127 2 113 8 96 4 79 5 62 7 117 8 7 0 117 8 111 1 93 9 76 7 59 4 62 115 7 6 1 115 7 115 7 115 7 98 9 82 1 65 2 108 6 7 0 108 6 108 6 108 6 91 3 7...

Page 19: ...1 43 7 79 8 10 9 79 8 79 8 71 5 55 8 40 2 62 81 1 9 8 81 1 81 1 91 3 75 9 60 6 45 2 73 0 10 9 73 0 73 0 73 0 73 0 57 4 41 7 57 84 4 9 9 84 4 84 4 83 1 67 7 52 3 37 0 78 0 10 9 78 0 78 0 76 8 61 1 45 5...

Page 20: ...5 67 133 5 7 1 133 5 123 4 105 7 90 1 74 5 125 5 8 1 125 5 120 4 103 5 86 6 69 8 62 124 4 7 0 124 4 124 4 124 4 108 8 93 2 77 6 117 0 8 0 117 0 117 0 117 0 100 2 83 3 66 4 57 126 7 7 0 126 7 126 7 12...

Page 21: ...0 65 2 48 4 92 3 12 7 92 3 92 3 79 0 62 0 44 9 62 96 1 11 3 96 1 96 1 96 1 79 3 62 5 45 7 86 9 12 5 86 9 86 9 86 9 70 8 53 7 36 7 57 101 9 11 4 101 9 101 9 93 8 77 0 60 2 43 4 93 6 12 7 93 6 93 6 85...

Page 22: ...9 3 190 9 169 3 147 0 124 7 102 4 179 7 10 3 179 7 165 0 142 5 119 9 97 3 62 167 4 9 2 167 4 167 4 167 4 145 1 122 8 100 5 160 9 10 2 160 9 160 9 160 9 138 3 115 8 93 2 57 174 9 9 3 174 9 174 9 174 9...

Page 23: ...7 128 2 15 3 128 2 124 0 105 0 86 1 67 1 62 138 7 13 7 138 7 138 7 127 5 108 5 89 5 70 5 132 0 15 0 132 0 132 0 119 0 100 1 81 1 62 2 57 135 4 13 7 135 4 135 4 126 8 107 8 88 8 69 8 128 2 15 1 128 2 1...

Page 24: ...1 6 3 6 5 6 7 6 9 7 1 7 4 7 6 80 MBH 13 0 24 9 36 7 48 6 60 4 72 3 84 2 96 0 KW 6 9 7 1 7 3 7 5 7 7 7 9 8 1 8 4 3000 55 MBH 20 1 32 0 43 8 55 7 67 6 79 4 91 3 103 2 KW 4 4 4 6 4 9 5 1 5 3 5 5 5 7 5 9...

Page 25: ...H 26 6 46 1 65 7 85 2 104 8 124 4 143 9 163 5 kW 8 44 8 82 9 21 9 60 9 99 10 38 10 76 11 15 70 MBH 22 5 42 0 61 6 81 2 100 7 120 3 139 8 159 4 kW 10 24 10 63 11 02 11 41 11 80 12 18 12 57 12 96 80 MBH...

Page 26: ...1072 1 87 1124 2 04 2400 631 0 16 682 0 41 736 0 66 793 0 90 852 1 14 911 1 36 970 1 58 1028 1 78 1084 1 97 1136 2 13 2600 642 0 27 692 0 52 747 0 76 804 1 01 862 1 24 922 1 47 981 1 69 1039 1 89 1094...

Page 27: ...ressure IWG1 1 Blower performance includes 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the ma...

Page 28: ...113 2 02 1153 2 24 2400 689 0 42 743 0 69 800 0 93 859 1 16 919 1 37 978 1 57 1035 1 77 1088 1 97 1135 2 18 1176 2 40 2600 712 0 60 766 0 87 823 1 11 882 1 34 942 1 55 1002 1 75 1058 1 95 1111 2 15 11...

Page 29: ...P RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Field Supplied Drive Standard 3 HP Drive Hi Static 5 HP Drive 3200 757 1 20 811 1 36 864 1 50 915 1 64 964 1 77 1012 1 89 1059 2 02 1104 2 14 1149 2 26 1192 2 38...

Page 30: ...4 0 14 0 07 0 08 0 09 0 10 0 13 2500 0 11 0 16 0 08 0 09 0 10 0 11 0 14 2700 0 18 0 17 0 09 0 10 0 12 0 13 0 16 2900 0 25 0 19 0 10 0 11 0 13 0 14 0 18 3100 0 31 0 20 0 12 0 13 0 15 0 16 0 20 3300 0 3...

Page 31: ...1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will...

Page 32: ...0 676 0 651 Electric Heat Minimum Supply Air Size Tons Model Voltage Minimum Supply Air CFM Heater kW 9 18 24 36 54 078 6 5 XP 208 230 3 60 1950 1950 1950 1950 460 3 60 1950 1950 1950 1950 600 3 60 19...

Page 33: ...1 3 4 2 2 2 8 5 3800 2PE04703258 575 1 60 3 4 1050 1 2 9 1 5 1 9 4 3800 Electric Heat Multipliers Voltage kW Capacity Multipliers1 1 Electric heaters are rated at nominal voltage Use this table to det...

Page 34: ...e with AHRI 270 standard Octave Band Centerline Frequency Hz 125 250 500 1000 2000 4000 8000 078 6 5 XP 83 88 0 82 5 81 5 78 0 73 0 69 0 62 0 090 7 5 XP 83 89 5 83 5 82 0 78 0 72 5 68 0 60 5 102 8 5 X...

Page 35: ...49 6 50 60 E09 6 8 1 18 9 67 7 73 2 70 80 E18 13 5 2 37 5 90 9 96 4 100 100 E24 18 2 50 0 106 6 112 1 110 125 E36 25 5 2 70 8 132 6 138 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 0 0 None 44 1 49 6 50 6...

Page 36: ...3 5 2 37 5 114 1 119 6 125 125 E24 18 2 50 0 129 8 135 3 150 150 E36 25 5 2 70 8 155 8 161 3 175 175 E54 40 6 2 112 7 155 8 161 4 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 0 0 None 67 3 72 8 80 90 E18...

Page 37: ...0 E09 6 8 1 18 9 71 3 76 8 80 80 E18 13 5 2 37 5 94 5 100 0 100 100 E24 18 2 50 0 110 2 115 7 125 125 E36 25 5 2 70 8 136 2 141 7 150 150 230 15 6 83 1 21 4 1 5 9 6 5 5 0 0 None 47 7 53 2 60 60 E09 9...

Page 38: ...13 5 2 37 5 119 3 124 8 125 125 E24 18 2 50 0 135 0 140 5 150 150 E36 25 5 2 70 8 161 0 166 5 175 175 E54 40 6 2 112 7 161 0 167 9 175 175 230 22 4 149 0 35 0 1 5 16 1 5 5 0 0 None 72 5 78 0 90 100 E1...

Page 39: ...E09 6 8 1 18 9 77 7 83 2 80 90 E18 13 5 2 37 5 100 9 106 4 110 110 E24 18 2 50 0 116 6 122 1 125 125 E36 25 5 2 70 8 142 6 148 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 10 0 None 54 1 59 6 60 70 E09 9...

Page 40: ...8 13 5 2 37 5 124 1 129 6 125 150 E24 18 2 50 0 139 8 145 3 150 150 E36 25 5 2 70 8 165 8 171 3 175 175 E54 40 6 2 112 7 167 0 173 9 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 10 0 None 77 3 82 8 90 100...

Page 41: ...E09 6 8 1 18 9 81 3 86 8 90 90 E18 13 5 2 37 5 104 5 110 0 110 110 E24 18 2 50 0 120 2 125 7 125 150 E36 25 5 2 70 8 146 2 151 7 150 175 230 15 6 83 1 21 4 1 5 9 6 5 5 10 0 None 57 7 63 2 70 70 E09 9...

Page 42: ...13 5 2 37 5 129 3 134 8 150 150 E24 18 2 50 0 145 0 150 5 150 175 E36 25 5 2 70 8 171 0 176 5 175 200 E54 40 6 2 112 7 173 5 180 4 175 200 230 22 4 149 0 35 0 1 5 16 1 5 5 10 0 None 82 5 88 0 100 110...

Page 43: ...528195 YTG I 0513 Johnson Controls Unitary Products 43 Typical Wiring Diagrams XP078 150 Typical Wiring Diagrams Typical XP078 120 Heat Pump with without Electric Heat Wiring Diagram...

Page 44: ...528195 YTG I 0513 44 Johnson Controls Unitary Products Typical XP150 Heat Pump with without Electric Heat Wiring Diagram...

Page 45: ...1085 1080 38 25 262 195 266 357 184 150 124 169 204 250 090 7 5 XP 1095 1090 38 23 243 181 284 381 171 139 115 181 217 267 102 8 5 XP 1142 1137 38 25 5 282 210 276 370 197 161 133 175 211 259 120 10...

Page 46: ...528195 YTG I 0513 46 Johnson Controls Unitary Products XP078 150 Unit Dimensions XP078 120 XP150 See detail A for drain location See detail A for drain location...

Page 47: ...0 3 16 24 3 16 17 3 16 6 3 16 120 50 3 4 89 30 3 16 24 3 16 17 3 16 6 3 16 150 50 3 4 119 1 2 30 3 16 24 3 16 17 3 16 6 3 16 5 3 8 3 4 FPT XP078 150 Unit Clearances Direction Distance in Direction Dis...

Page 48: ...it Electrical Entry XP078 120 Unit Side Duct Openings Disconnect Swith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot...

Page 49: ...eft Duct Opening Side Duct Dimensions Unit Model Number Dimension in A B C D 078 28 1 4 18 1 16 28 1 4 18 1 4 090 28 1 4 18 1 16 28 1 4 18 1 4 102 28 1 4 18 1 16 28 1 4 18 1 4 120 28 1 4 18 1 16 28 1...

Page 50: ...ons XP078 150 Roof Curb XP078 150 Transition Roof Curb 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATED DECK UNDER COMPRESSOR SECTION INSULATED DECK UNDER CONDENSER SECTION FRONT RIGHT SUPPLY RETURN 7...

Page 51: ...2 UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME INSULATION UNIT BASE RAILS COUNTERFLASHING CAN T STRIP INSULATION AND ROOFING MATERIAL ROOF DECK AND SUPPORT STRUCTURE 14 3 56 3 75 XP078 1...

Page 52: ...n 42 Slab Economizer 42 tall cabinet 2EE047058242 50 Slab Economizer 50 tall cabinet 2EE047057242 1 Barometric relief must be ordered separately and installed in duct work 2 Barometric relief or fresh...

Page 53: ...ust 1EH0408 Barometric Relief Hood 1EH0408 Barometric Relief Damper 2PE047032XX Power Exhaust 2EE04706024 Fresh Air Hood 2EE04706024 Fresh Air Damper 2EE04706024 Return Air Damper Field Installed Duct...

Page 54: ...s reserved Supersedes 528195 YTG H 0213 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 Slab Economizer End Return W Power Exhaust 2EE04705X24 Slab Economizer 1EH0409 Barometric Reli...

Reviews: