Johnson Controls Unitary Products

Electric Heaters 

- The electric heaters range from 9kW to 

54kW and are available in all the voltage options of the 
base units. All heaters are dual staged. All heaters are 
intended for single point power supply.

• IntelliSpeed™ Supply Fan Control Option (ASHRAE 

90.1 compliant, section 6.4.3.10) - 

Units configured with 

the 

IntelliSpeed

  Supply Fan Option will contain a VFD 

for variable volume supply fan operation. This option 
allows the supply fan RPM to vary based on the number 
of compressors or heating stages energized. The 
economizer's minimum position will also be configurable 
to vary based on the supply fan VFD frequency output.

Disconnect Switch 

- For heat pump units with electric 

heat, a HACR breaker sized to the unit is provided. For 
heat pump units, a switch sized to the largest electric heat 
available for the particular unit is provided. Factory 
installed option only.

Convenience Outlet - (Non-Powered/Powered)

 - This 

option locates a 120V single-phase GFCI outlet with cover, 
on the corner of the unit housing adjacent to the 
compressors. The “Non-powered” option requires the 
installer to provide the 120V single-phase power source and 
wiring. The “Powered” option is powered by a stepdown 
transformer in the unit. Factory installed option only.

Smoke Detectors 

- The smoke detectors stop operation 

of the unit by interrupting power to the control board if 
smoke is detected within the air compartment. Available 
for both the supply and/or return air.

Filters

 – 2” Pleated MERV 7 or 4” Pleated MERV 13 are 

available to meet LEED requirements. A 2” Throwaway is 
shipped as standard.

Phase Monitors 

- Designed to prevent unit damage. The 

phase monitor will shut the unit down in an out-of phase 
condition. 

(Standard on units with Scroll Compressors.)

Coil Guard 

- Customers can purchase a coil guard kit to 

protect the condenser coil from damage. Additionally, this 
kit stops animals and foreign objects from entering the 
space between the inner condenser coil and the main 
cabinet. This is not a hail guard kit.

Dirty Filter Switch 

- This kit includes a differential 

pressure switch that energizes the fault light on the unit 
thermostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option or 
field installed accessory.

Technicoat Condenser Coils 

- The condenser coils are 

coated with a phenolic coating for protection against 
corrosion due to harsh environments.

Technicoat Evaporator Coil 

- The evaporator coils are 

coated with a phenolic coating for protection against 
corrosion due to harsh environments.

ElectroFin® E-coat Condenser Coils

 - The condenser 

coils are coated with an epoxy polymer coating to protect 
against corrosion.

ElectroFin® E-coat Evaporator Coils

 - The evaporator 

coils are coated with an epoxy polymer coating to protect 
against corrosion.

Control Options

BAS - Building Automation System Controls 

Simplicity

®

 

INTELLI-Comfort II™ Control - 

The York

®

 

Simplicity

®

 

INTELLI-Comfort II™ control is factory installed. It includes 
a supply air sensor, a return air sensor, and an outside air 
sensor. There are provisions for a field installed dirty filter 
indicator switch, an air-proving switch, an Outside Air 
Humidity sensor, a Return Air Humidity sensor, an Inside 
IAQ sensor, and an Outside Air IAQ sensor. Construction 
mode operation, 365-day real time clock with 7 day 
programming plus holiday scheduling is built-in. Two 
different modes of demand ventilation are achieved through 
the INTELLI-Comfort II™ using CO

2

 sensors. It uses an 

inside CO

2

 sensor to perform Demand Ventilation. It can 

also use an Outside CO

2

 sensor to perform Differential 

Demand Ventilation. It uses a Patented Comfort Ventilation 
algorithm to provide comfortable ventilation air 
temperature. The patented economizer-loading algorithm 
will protect the equipment when harsh operating conditions 
exist. It uses the INTELLI-Start™ algorithm to maximize 
energy savings by recovering the building from the 
Unoccupied Setpoints to the Occupied Setpoints just in 
time for the Occupied Time Period to begin. The 

Simplicity

®

 INTELLI-Comfort II™ balances space 

temperature, ventilation air temperature and CO

2

.

Simplicity

®

 INTELLI-Comfort II™ Control -

 The York® 

Simplicity

®

 INTELLI-Comfort II™ control is factory 

installed. It includes all the features of the INTELLI-
Comfort II™ control with an additional control to translate 
communications from MODBUS to the BACnet MSTP 
protocol.

Novar® BAS Control -

 The Novar® building automation 

system controller is factory installed. Incudes supply air 
sensor, return air sensor, dirty filter indicator switch, and 
air proving switch.

Johnson Controls BAS Control -

 The Johnson Control 

YK-UNT-1126 building automation system controller is 
factory installed. Includes supply air sensor, return air 
sensor, dirty filter indicator switch, and air proving switch.

CPC BAS Control - 

The Computer Process Controls 

Model 810-3060 ARTC Advanced Rooftop building 
automation system controller is factory installed. Includes 
supply air sensor, return air sensor, dirty filter indicator 
switch and air proving switch.

Honeywell BAS Control - 

The Honeywell W7750C 

building automation system controller is factory installed. 
Includes air supply sensor, return air sensor, dirty filter 
indicator switch, and air proving switch.

Factory installed smoke detectors in the return air, may be 
subjected to freezing temperatures during "off" times due 
to out side air infiltration. These smoke detectors have an 
operational limit of 32 °F to 131°F. Smoke detectors 
installed in areas that could be out side those limitations 
will have to be moved to prevent having false alarms.

Summary of Contents for Predator XP Series

Page 1: ...s are self contained and assembled on rigid full perimeter base rails allowing for 3 way forklift access and overhead rigging Every unit is completely charged wired piped and tested at the factory to...

Page 2: ...3 4 NPT Female Connection Belt drive blower motor Condenser section Filter drier solid core Filter access 2 or 4 filter options Disconnect location optional disconnect switch Compressor 2 Access High...

Page 3: ...ions 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S...

Page 4: ...rocating compressors Scroll compressors do not require crankcase heaters Phase Monitors are standard on units with scroll compressors This accessory monitors the incoming power to the unit and protect...

Page 5: ...or air As the outdoor air intake dampers open the return air dampers close The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input There...

Page 6: ...rrosion ElectroFin E coat Evaporator Coils The evaporator coils are coated with an epoxy polymer coating to protect against corrosion Control Options BAS Building Automation System Controls Simplicity...

Page 7: ...unit with a down flow economizer Power exhaust plugs into the connector in the unit bulkhead You must purchase 1EH0408 barometric relief when applying to a horizontal flow application Manual Outdoor A...

Page 8: ...Motorized Damper Horizontal Incl Hood Damper Filter no Barometric Relief 2EE04705924 Economizer Downflow Incl Barometric Relief All Hoods 2EE04706024 Economizer Horizontal Incl Dampers Hoods no Barom...

Page 9: ...nd be accessible through hinged access door Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without rem...

Page 10: ...ailable by either or ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER Outdoor and return air dampers that are interlocked and positioned by a fully modulating spring return damper actuator The maximum leakage...

Page 11: ...t available SMOKE DETECTOR A smoke detector can be factory mounted and wired in the supply and or return air compartments OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF CURB 14 and 8 high full perime...

Page 12: ...7 3 35 7 9 3 35 8 6 3 30 13 2 3 0 17 F capacity rating Mbh 43 0 51 0 53 0 58 0 90 0 System power KW COP 5 7 2 20 6 4 2 25 6 9 2 25 7 8 2 20 13 5 2 2 HSPF Btu Watts hr DIMENSIONS inches Length 89 89 89...

Page 13: ...1725 Frame size 56 56 56 56 56 56 56 56 56 184T FILTERS Quantity Size 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 1 2 4 24 x 20 x 2 3 4 24 x 20 x 4 3 4 24 x 2...

Page 14: ...121 3 4 9 90 6 76 7 62 9 49 1 111 6 5 5 88 1 74 1 60 1 46 1 67 111 3 4 9 111 3 93 3 79 5 65 6 51 8 101 6 5 5 101 6 89 9 75 9 61 9 47 9 62 99 9 4 8 99 9 99 9 97 3 83 5 69 6 55 8 92 3 5 4 92 3 92 3 91...

Page 15: ...6 67 3 8 6 67 3 64 1 53 0 41 8 30 7 62 68 8 7 8 68 8 68 8 66 5 55 1 43 7 32 3 61 6 8 6 61 6 61 6 61 1 49 9 38 8 27 6 57 70 6 7 7 70 6 70 6 67 2 55 8 44 4 33 0 65 0 8 5 65 0 65 0 61 6 50 4 39 3 28 1 2...

Page 16: ...64 0 50 0 113 1 6 5 88 6 74 7 60 8 46 9 67 112 3 5 7 112 3 97 9 83 9 69 9 55 9 103 5 6 5 103 5 94 5 80 6 66 7 52 8 62 106 2 5 6 106 2 106 2 106 2 92 2 78 2 64 2 96 4 6 4 96 4 96 4 96 4 82 5 68 6 54 7...

Page 17: ...9 68 7 10 0 68 7 68 7 58 2 47 1 36 0 62 72 5 9 0 72 5 72 5 73 8 62 5 51 2 39 9 65 9 9 9 65 9 65 9 65 9 57 6 46 6 35 5 57 72 0 9 0 72 0 72 0 74 4 63 1 51 8 40 5 65 2 9 9 65 2 65 2 65 2 57 1 46 0 34 9...

Page 18: ...8 74 9 58 1 128 6 7 1 106 2 89 0 71 8 54 5 67 127 2 6 2 127 2 113 8 96 4 79 5 62 7 117 8 7 0 117 8 111 1 93 9 76 7 59 4 62 115 7 6 1 115 7 115 7 115 7 98 9 82 1 65 2 108 6 7 0 108 6 108 6 108 6 91 3 7...

Page 19: ...1 43 7 79 8 10 9 79 8 79 8 71 5 55 8 40 2 62 81 1 9 8 81 1 81 1 91 3 75 9 60 6 45 2 73 0 10 9 73 0 73 0 73 0 73 0 57 4 41 7 57 84 4 9 9 84 4 84 4 83 1 67 7 52 3 37 0 78 0 10 9 78 0 78 0 76 8 61 1 45 5...

Page 20: ...5 67 133 5 7 1 133 5 123 4 105 7 90 1 74 5 125 5 8 1 125 5 120 4 103 5 86 6 69 8 62 124 4 7 0 124 4 124 4 124 4 108 8 93 2 77 6 117 0 8 0 117 0 117 0 117 0 100 2 83 3 66 4 57 126 7 7 0 126 7 126 7 12...

Page 21: ...0 65 2 48 4 92 3 12 7 92 3 92 3 79 0 62 0 44 9 62 96 1 11 3 96 1 96 1 96 1 79 3 62 5 45 7 86 9 12 5 86 9 86 9 86 9 70 8 53 7 36 7 57 101 9 11 4 101 9 101 9 93 8 77 0 60 2 43 4 93 6 12 7 93 6 93 6 85...

Page 22: ...9 3 190 9 169 3 147 0 124 7 102 4 179 7 10 3 179 7 165 0 142 5 119 9 97 3 62 167 4 9 2 167 4 167 4 167 4 145 1 122 8 100 5 160 9 10 2 160 9 160 9 160 9 138 3 115 8 93 2 57 174 9 9 3 174 9 174 9 174 9...

Page 23: ...7 128 2 15 3 128 2 124 0 105 0 86 1 67 1 62 138 7 13 7 138 7 138 7 127 5 108 5 89 5 70 5 132 0 15 0 132 0 132 0 119 0 100 1 81 1 62 2 57 135 4 13 7 135 4 135 4 126 8 107 8 88 8 69 8 128 2 15 1 128 2 1...

Page 24: ...1 6 3 6 5 6 7 6 9 7 1 7 4 7 6 80 MBH 13 0 24 9 36 7 48 6 60 4 72 3 84 2 96 0 KW 6 9 7 1 7 3 7 5 7 7 7 9 8 1 8 4 3000 55 MBH 20 1 32 0 43 8 55 7 67 6 79 4 91 3 103 2 KW 4 4 4 6 4 9 5 1 5 3 5 5 5 7 5 9...

Page 25: ...H 26 6 46 1 65 7 85 2 104 8 124 4 143 9 163 5 kW 8 44 8 82 9 21 9 60 9 99 10 38 10 76 11 15 70 MBH 22 5 42 0 61 6 81 2 100 7 120 3 139 8 159 4 kW 10 24 10 63 11 02 11 41 11 80 12 18 12 57 12 96 80 MBH...

Page 26: ...1072 1 87 1124 2 04 2400 631 0 16 682 0 41 736 0 66 793 0 90 852 1 14 911 1 36 970 1 58 1028 1 78 1084 1 97 1136 2 13 2600 642 0 27 692 0 52 747 0 76 804 1 01 862 1 24 922 1 47 981 1 69 1039 1 89 1094...

Page 27: ...ressure IWG1 1 Blower performance includes 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the ma...

Page 28: ...113 2 02 1153 2 24 2400 689 0 42 743 0 69 800 0 93 859 1 16 919 1 37 978 1 57 1035 1 77 1088 1 97 1135 2 18 1176 2 40 2600 712 0 60 766 0 87 823 1 11 882 1 34 942 1 55 1002 1 75 1058 1 95 1111 2 15 11...

Page 29: ...P RPM BHP RPM BHP RPM BHP RPM BHP 3 HP Field Supplied Drive Standard 3 HP Drive Hi Static 5 HP Drive 3200 757 1 20 811 1 36 864 1 50 915 1 64 964 1 77 1012 1 89 1059 2 02 1104 2 14 1149 2 26 1192 2 38...

Page 30: ...4 0 14 0 07 0 08 0 09 0 10 0 13 2500 0 11 0 16 0 08 0 09 0 10 0 11 0 14 2700 0 18 0 17 0 09 0 10 0 12 0 13 0 16 2900 0 25 0 19 0 10 0 11 0 13 0 14 0 18 3100 0 31 0 20 0 12 0 13 0 15 0 16 0 20 3300 0 3...

Page 31: ...1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will...

Page 32: ...0 676 0 651 Electric Heat Minimum Supply Air Size Tons Model Voltage Minimum Supply Air CFM Heater kW 9 18 24 36 54 078 6 5 XP 208 230 3 60 1950 1950 1950 1950 460 3 60 1950 1950 1950 1950 600 3 60 19...

Page 33: ...1 3 4 2 2 2 8 5 3800 2PE04703258 575 1 60 3 4 1050 1 2 9 1 5 1 9 4 3800 Electric Heat Multipliers Voltage kW Capacity Multipliers1 1 Electric heaters are rated at nominal voltage Use this table to det...

Page 34: ...e with AHRI 270 standard Octave Band Centerline Frequency Hz 125 250 500 1000 2000 4000 8000 078 6 5 XP 83 88 0 82 5 81 5 78 0 73 0 69 0 62 0 090 7 5 XP 83 89 5 83 5 82 0 78 0 72 5 68 0 60 5 102 8 5 X...

Page 35: ...49 6 50 60 E09 6 8 1 18 9 67 7 73 2 70 80 E18 13 5 2 37 5 90 9 96 4 100 100 E24 18 2 50 0 106 6 112 1 110 125 E36 25 5 2 70 8 132 6 138 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 0 0 None 44 1 49 6 50 6...

Page 36: ...3 5 2 37 5 114 1 119 6 125 125 E24 18 2 50 0 129 8 135 3 150 150 E36 25 5 2 70 8 155 8 161 3 175 175 E54 40 6 2 112 7 155 8 161 4 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 0 0 None 67 3 72 8 80 90 E18...

Page 37: ...0 E09 6 8 1 18 9 71 3 76 8 80 80 E18 13 5 2 37 5 94 5 100 0 100 100 E24 18 2 50 0 110 2 115 7 125 125 E36 25 5 2 70 8 136 2 141 7 150 150 230 15 6 83 1 21 4 1 5 9 6 5 5 0 0 None 47 7 53 2 60 60 E09 9...

Page 38: ...13 5 2 37 5 119 3 124 8 125 125 E24 18 2 50 0 135 0 140 5 150 150 E36 25 5 2 70 8 161 0 166 5 175 175 E54 40 6 2 112 7 161 0 167 9 175 175 230 22 4 149 0 35 0 1 5 16 1 5 5 0 0 None 72 5 78 0 90 100 E1...

Page 39: ...E09 6 8 1 18 9 77 7 83 2 80 90 E18 13 5 2 37 5 100 9 106 4 110 110 E24 18 2 50 0 116 6 122 1 125 125 E36 25 5 2 70 8 142 6 148 1 150 150 230 15 6 83 1 21 4 1 5 6 0 5 5 10 0 None 54 1 59 6 60 70 E09 9...

Page 40: ...8 13 5 2 37 5 124 1 129 6 125 150 E24 18 2 50 0 139 8 145 3 150 150 E36 25 5 2 70 8 165 8 171 3 175 175 E54 40 6 2 112 7 167 0 173 9 175 175 230 22 4 149 0 35 0 1 5 10 9 5 5 10 0 None 77 3 82 8 90 100...

Page 41: ...E09 6 8 1 18 9 81 3 86 8 90 90 E18 13 5 2 37 5 104 5 110 0 110 110 E24 18 2 50 0 120 2 125 7 125 150 E36 25 5 2 70 8 146 2 151 7 150 175 230 15 6 83 1 21 4 1 5 9 6 5 5 10 0 None 57 7 63 2 70 70 E09 9...

Page 42: ...13 5 2 37 5 129 3 134 8 150 150 E24 18 2 50 0 145 0 150 5 150 175 E36 25 5 2 70 8 171 0 176 5 175 200 E54 40 6 2 112 7 173 5 180 4 175 200 230 22 4 149 0 35 0 1 5 16 1 5 5 10 0 None 82 5 88 0 100 110...

Page 43: ...528195 YTG I 0513 Johnson Controls Unitary Products 43 Typical Wiring Diagrams XP078 150 Typical Wiring Diagrams Typical XP078 120 Heat Pump with without Electric Heat Wiring Diagram...

Page 44: ...528195 YTG I 0513 44 Johnson Controls Unitary Products Typical XP150 Heat Pump with without Electric Heat Wiring Diagram...

Page 45: ...1085 1080 38 25 262 195 266 357 184 150 124 169 204 250 090 7 5 XP 1095 1090 38 23 243 181 284 381 171 139 115 181 217 267 102 8 5 XP 1142 1137 38 25 5 282 210 276 370 197 161 133 175 211 259 120 10...

Page 46: ...528195 YTG I 0513 46 Johnson Controls Unitary Products XP078 150 Unit Dimensions XP078 120 XP150 See detail A for drain location See detail A for drain location...

Page 47: ...0 3 16 24 3 16 17 3 16 6 3 16 120 50 3 4 89 30 3 16 24 3 16 17 3 16 6 3 16 150 50 3 4 119 1 2 30 3 16 24 3 16 17 3 16 6 3 16 5 3 8 3 4 FPT XP078 150 Unit Clearances Direction Distance in Direction Dis...

Page 48: ...it Electrical Entry XP078 120 Unit Side Duct Openings Disconnect Swith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot...

Page 49: ...eft Duct Opening Side Duct Dimensions Unit Model Number Dimension in A B C D 078 28 1 4 18 1 16 28 1 4 18 1 4 090 28 1 4 18 1 16 28 1 4 18 1 4 102 28 1 4 18 1 16 28 1 4 18 1 4 120 28 1 4 18 1 16 28 1...

Page 50: ...ons XP078 150 Roof Curb XP078 150 Transition Roof Curb 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATED DECK UNDER COMPRESSOR SECTION INSULATED DECK UNDER CONDENSER SECTION FRONT RIGHT SUPPLY RETURN 7...

Page 51: ...2 UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME INSULATION UNIT BASE RAILS COUNTERFLASHING CAN T STRIP INSULATION AND ROOFING MATERIAL ROOF DECK AND SUPPORT STRUCTURE 14 3 56 3 75 XP078 1...

Page 52: ...n 42 Slab Economizer 42 tall cabinet 2EE047058242 50 Slab Economizer 50 tall cabinet 2EE047057242 1 Barometric relief must be ordered separately and installed in duct work 2 Barometric relief or fresh...

Page 53: ...ust 1EH0408 Barometric Relief Hood 1EH0408 Barometric Relief Damper 2PE047032XX Power Exhaust 2EE04706024 Fresh Air Hood 2EE04706024 Fresh Air Damper 2EE04706024 Return Air Damper Field Installed Duct...

Page 54: ...s reserved Supersedes 528195 YTG H 0213 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 Slab Economizer End Return W Power Exhaust 2EE04705X24 Slab Economizer 1EH0409 Barometric Reli...

Reviews: