background image

ELECTRICAL CONNECTIONS

GENERAL INFORMATION & GROUNDING 

Check the electrical supply to be sure that it meets the values
specified on the unit nameplate and wiring label.

Power wiring, control (low voltage) wiring, disconnect switches
and overcurrent protection to be supplied by the installer. See
Table 1 for proper sizes. Wire size should be at least equal to
or greater than the size shown in Table 1.

CAUTION: All field wiring must USE COPPER CONDUC-

TORS ONLY and be in accordance with Local,
National Fire, Safety & Electrical Codes. This
unit must be grounded with a separate ground
wire in accordance with the above codes.

The complete connection diagram and schematic wiring label
is located on the inside surface of the unit electrical box cover.
Field wiring is also shown in Figure 1. 

NOTE:  The wires for the operation of the lead compressor are

solid in color. For differentiation, the wires of the fol-
lower compressor are basically the same in color, but
striped.

POWER WIRING

1. Install the proper size weatherproof disconnect switch out-

doors and within sight of the unit.

2. Run power wiring from the disconnect switch to the unit.

3. Remove the control box cover to gain access to the unit

wiring. Route wires from disconnect through power wiring
opening provided and  into the unit control box as shown in
Figure 8.

4. Install the proper size time-delay fuses or circuit breaker,

and make the power supply connections.

5. Energize the crankcase heater to save time by preheating

the compressor oil while the remaining installation is com-
pleted.

ACCESSORY WIRING

The electrical accessories available for this unit are a two stage
cooling thermostat and an optional De-humidification Control.
Refer to the individual instructions packaged with the accesso-
ries for installation.

THERMOSTAT MOUNTING / WIRING

This condensing unit must be installed with the factory recom-
mended thermostat, 2ET04700224 or any conventional two-
stage cooling thermostat. The difference between the two
stages of a typical two-stage thermostat is 2 - 2.5 

°

F. 

The thermostat should be located about 5 ft. above the floor,
where it will be exposed to normal room air circulation. Do not
place it on an outside wall or where it is exposed to the radiant
effect from exposed glass or appliances, drafts from outside
doors or supply air grilles.

After the thermostat is mounted, route the 24-volt control wiring
(NEC Class 2) from the thermostat to the indoor varible speed
air handler and outdoor unit.  Route the control wiring into the
grommetted hole in the bottom of control box of the outdoor
unit. Using wire nuts connect to leads provided in unit control
box as per Figure 8.  

Interconnecting control wiring must be a minimum of No. 18
AWG color coded insulated wires. If wire lengths increase more
than 90 feet, use No. 16 AWG wires, to prevent excessive
voltage drop.

NOTE:  To eliminate erratic operation, seal the hole in the wall

at the thermostat with permagum or equivalent to
prevent air drafts affecting the anticipators in the
thermostat.

DE-HUMIDIFICATION CONTROL

A de-humidification control accessory 2HU06700124 may be
required in high humidity areas. This control provides cooling
at a reduced air flow, lowering evaporator temperature and
increasing latent capacity. To install, refer to instructions pack-
aged with the accessory. Prior to the installation of the de-hu-
midification control, the jumper across the de-humidification
control terminals on the indoor variable speed air handler
terminal board must be removed. See Figure 10.  Refer to
Figure 9 for wiring details.

During first or second stage cooling, if the relative humidity in
the space is higher than the desired set point of the de-humidi-
fication control, the variable speed blower motor will operate at
a lower speed until the de-humidification control is satisfied.  A
40 - 60% relative humidity level is recommended to achieve
optimum comfort.

NOTE: If a de-humidification control is installed, it is recom-

mended  that a minimum  air flow of 325 cfm/ton be
supplied at all times.

550.37-N1Y

6

Central Environmental Systems

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: