background image

PIPING CONNECTIONS

The outdoor condensing unit may be connected to the indoor
evaporator coil using field supplied refrigerant grade copper
tubing that is internally clean and dry. Units  should be installed
only with the tubing sizes for approved system combinations
as specified in Table 5. The charge given is applicable for total
tubing lengths up to 15 feet. See Application Data Form 690.01-
AD1V for installing tubing of longer lengths and elevation
differences.

NOTE: Using a larger than specified line size could result in

oil return problems. Using too small a line will result in
loss of capacity and other problems caused by insuffi-
cient refrigerant flow. Slope horizontal vapor lines at
least 1" every 20 feet toward the  outdoor unit to
facilitate proper oil return.

PRECAUTIONS DURING LINE INSTALLATION

1. Install the lines with as few bends as possible. Care must

be taken not to damage the couplings or kink the tubing.
Use clean hard drawn copper tubing where no appreciable
amount of bending around obstruction is necessary. If soft
copper must be used, care must be taken to avoid sharp
bends which may cause a restriction.

2. The lines should be installed so that they will not obstruct

service access to the coil, air handling system or filter.

3. Care must also be taken to isolate the refrigerant lines to

minimize noise transmission from the equipment to the struc-
ture.

4. The vapor line must be insulated with a minimum of 1/2"

foam rubber insulation (Arm-A-Flex or equivalent). Liquid
lines that will be exposed to direct sunlight and/or high
temperatures must also be insulated.

5. Tape and suspend the refrigerant lines as shown. DO NOT

allow metal-to metal contact. See Figure 4.

6. Use PVC piping as a conduit for all underground installa-

tions as shown in Figure 5. Buried lines should be kept as
short as possible to minimize the build up of liquid refriger-
ant in the vapor line during long periods of shutdown.

7. Pack fiber glass insulation and a sealing material such as

permagum around refrigerant lines where they penetrate a
wall to reduce vibration and to retain some flexibility.

8. See Form 690.01-AD1V for additional piping information.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-
copper and should be brazed with a phosphorous-copper alloy
material such as Silfos-5 or equivalent. DO NOT use soft
solder.

CAUTION: Dry nitrogen should always be supplied through the

tubing while it is being brazed, because the tempera-
ture required is high enough to cause oxidation of the
copper unless an inert atmosphere is provided. The
flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety
valve to insure that only low pressure dry nitrogen is
introduced into the tubing. Only a small flow is nec-
essary to displace air and prevent oxidation.

The outdoor units have re-usable service valves on both the
liquid and vapor connections.  The total system refrigerant
charge is retained within the outdoor unit during shipping and
installation. The re-usable service valves are provided to
evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate
precautions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING ANGLE VALVE 

Precautions should be taken to prevent heat damage to angle
valve by wrapping a wet rag around it as shown in Figure 6.
Also, protect all painted surfaces and insulation during brazing.
After brazing - cool joint with wet rag.

WARNING: This is not a backseating valve. The service access

port has a valve core. Opening or closing valve
does not close service access port.

Valve can be opened by removing the plunger cap (See Figure
7) and fully inserting a hex wrench into the stem and backing
out counter-clockwise until valve stem just touches retaining ring.

FIGURE 4 - TUBING HANGER

LIQUID

LINE

TAPE

SHEET
METAL
HANGER

INSULATED
VAPOR LINE

TO INDOOR COIL

TO OUTDOOR UNIT

LIQUID LINE

CAP

PVC

CONDUIT

INSULATED

VAPOR LINE

FIGURE 5 - UNDERGROUND INSTALLATION

550.37-N1Y

4

Central Environmental Systems

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: