background image

All outdoor wiring must be
weatherproof. Use copper
conductors only.

POWER WIRING
   208/230-1-60

C ON TA C TOR

G RD .
S C RE W

M 2

T 1

L 1

L 2

OUTDOOR UNIT

T 2

C ON TA C TOR

M 1

T 1

L 1

L 2

T 2

TYPICAL
TWO STAGE
COOLING
THERMOSTAT
MUST BE
USED

POWER

CONTROL

FACTORY

WIRE NUT

BRN

YEL

BLU

BLK

I N DO O R  
VARIABLE SPE ED AIR
HA NDL E R / F URN ACE
T ERMI NA L  B OAR D

RED

W1

G

W2

C

R

Y2

Y1

Y

G

W2

BK

X

O

C

R

Y2

Y1

C

R

Y2

Y1

Y2 OUT

W/W1

DE-HUMIDIFICATION
CONTROL CONNECTION
(JUMPER MUST BE REMOVED)

FOR ELECTRIC HEAT ONLY

(CLASS 2 WIRING)

(CLASS 1 WIRING)

FIGURE 8 - TYPICAL FIELD WIRING

POWER 
WIRING

CONTROL 
WIRING

COOLING
WITH
DE-HUMIDIFICATION
CONTROL

FIGURE 9 - TYPICAL FIELD  WIRING WITH

POWER WIRING
   208/230-1-60

C ON TA C TOR

G RD .
S C RE W

M 2

T 1

L 1

L 2

OUTDOOR UNIT

T 2

C ON TA C TOR

M 1

T 1

L 1

L 2

T 2

TYPICAL
TWO STAGE
COOLING
THERMOSTAT
MUST BE
USED

POWER

CONTROL

FACTORY

WIRE NUT

BRN

YEL

BLU

BLK

I N DO O R  
VA RIAB LE SPEED AIR
HA NDL ER /  FUR NACE
T ERMI NAL  BOA RD

RED

W1

G

W2

C

R

Y2

Y1

Y

G

W2

BK

X

O

C

R

Y2

Y1

C

R

Y2

Y1

Y2 OUT

W/W1

FOR ELECTRIC HEAT ONLY

(CLASS 2 WIRING)

(CLASS 1 WIRING)

COOLING
ONLY

ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND/OR LOCAL CODES.

DE-HUMIDIFICATION CONTROL

550.37-N1Y

Central Environmental Systems

7

Summary of Contents for H1DS048

Page 1: ...nce with all national and local safety codes and the limitations listed below 1 Limitations for the indoor unit coil and appropriate acces sories must also be observed 2 This unit should not be instal...

Page 2: ...mpressor RATED LOAD 8 3 8 3 10 9 LOCKED ROTOR 48 48 64 COMPRESSOR 2 AMPS Follower Compressor RATED LOAD 9 0 13 5 15 1 LOCKED ROTOR 48 68 81 0 CRANKCASE HEATER YES YES YES FAN MOTORAMPS RATED LOAD 0 7...

Page 3: ...ioned as shown in Figure 2 to reduce noise and allow for proper drainage 6 Make a hole s in the structure wall large enough to acco modate the insulated vapor line the liquid line and the wiring TXV I...

Page 4: ...insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 8 See Form 690 01 AD1V for additional piping...

Page 5: ...vaporator and the liquid line to 1000 microns or less 8 Leak test all refrigerant piping connections including the serv ice port flare caps to be sure they are leak tight DO NOT OVERTIGHTEN between 40...

Page 6: ...oling thermostat The difference between the two stages of a typical two stage thermostat is 2 2 5 F The thermostat should be located about 5 ft above the floor where it will be exposed to normal room...

Page 7: ...SS 1 WIRING FIGURE 8 TYPICAL FIELD WIRING POWER WIRING CONTROL WIRING COOLING WITH DE HUMIDIFICATION CONTROL FIGURE 9 TYPICAL FIELD WIRING WITH POWER WIRING 208 230 1 60 CONTACTOR GRD SCREW M 2 T 1 L...

Page 8: ...OR VARIABLE SPEED AIR HANDLER INDOOR EVAP COIL CONDENSING UNITS H DS036 H DS048 H DS060 COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE COOL TAP ADJ TAP DELAY PROFILE N1VSD14 G HC036 Jum...

Page 9: ...r the first time Refer to System Functions for more information about time delays 2 Operate the unit for a minimum of 15 20 minutes before checking the charge 3 Verify the desired indoor air handler a...

Page 10: ...e until the recommended sub cooling temperature is obtained EXAMPLE Given an H1DS036 with only the lead compressor operating on first stage 1 Liquid pressure at the service valve 179 lbs 2 Recommended...

Page 11: ...des a list of LED functions and definitions Power Supply The five minute control board time delay is energized by means of 24V power supply from the transformer installed in the indoor variable speed...

Page 12: ...oor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discharging cool air from the ducts 3 The vapor line at t...

Reviews: